Daikin FTXS60GV1B Service Manual page 109

Inverter pair wall mounted type
Hide thumbs Also See for FTXS60GV1B:
Table of Contents

Advertisement

SiBE041011EC
Troubleshooting
Check No.17
Refer to P.106
Check No.19
Refer to P.107
RK(X)S60F3V1B
RK(X)S60F3V1B9
RXS60F4V1B
71 class
Note:
Refer to Silicon Grease on Power Transistor / Diode Bridge on page 117 for detail.
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power. Then, turn on
the power to restart the system.
Error displayed again?
NO
Check No. 19
Check the outdoor fan.
OK
Radiation fin dirty?
YES
A (°C)
YES
Has the PCB been
replaced?
NO
Check the radiation fin
temperature.
Above A ˚C?
YES
NG
NO
105
85
105
Troubleshooting
YES
Check if silicon grease is
applied properly on the
radiation fin. If not, apply
the silicon grease.
NO
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors and
fan motor leads.
Replace the outdoor unit
PCB (main PCB).
Check the installation
condition.
Go to Check No. 17.
Clean up the radiation fin.
(R21437)
98