14
10 REGTRONIC PE Specifications
Casing
Material
Dimensions (L x W x H) in mm,
weight
Protection class
Electrical specifications
Supply voltage
Radio interference class
Max. cable cross-section, 230 V
connections
Temperature sensor
Measuring range
Test voltage
Output Voltage
Power - switching output
Fuse protection
Miscellaneous
Operating temperature
Storage temperature
Humidity
11 Resistance table PT1000
Temperature sensors can be checked for proper function by using an ohmmeter
and consulting the following temperature resistance table:
Temperature
in °C
-30
-20
-10
0
10
20
30
40
50
100% recyclable ABS casing for wall mounting
175 x 134 x 56; approx. 360 g
IP20 according to DIN 40050, IEC 529, VDE
0470,
EN 60529
AC 230 V/50 Hz, -10 – +15%
N (as defined by VDE 0875)
2.5 mm² fine-/single-wire
PT1000, 1 kΩ at 0 °C
- 30 °C .. +250 °C
4 kV 1 min according to EN 60730/DIN, VDE
0631, IEC 60664/IEC
230V~
1A / approx. 230VA for cos φ = 0,7-1,0
Fine-wire fuses 5 x 20mm, 2A/T
(2 amperes, delayed-action fuse)
0 – 50°C
-10 – +65°C
max. 60 %
Resistance
Temperature
in Ohm
882
921
960
1000
1039
1077
1116
1155
1194
Resistance
in °C
in Ohm
60
1232
70
1271
80
1309
90
1347
100
1385
120
1461
140
1535
200
1758