Checking Correct Grounding; Testing Operations - Samsung AC030JXADCH Installation Manual

Hide thumbs Also See for AC030JXADCH:
Table of Contents

Advertisement

Checking correct grounding

If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an
grounding electrode must be installed . The corresponding accessories are not supplied with the air conditioner .
1 . Select an grounding electrode that complies with the specifications given in
the illustration .
2 . Connect the flexible hose to the flexible hose port .
f In damp hard soil rather than loose sandy or gravel soil that has a higher
f
grounding resistance .
f Away from underground structures or facilities, such as gas pipes, water
f
pipes, telephone lines and underground cables .
f At least two metres away from a lightening conductor grounding electrode
f
and its cable .
• The grounding wire for the telephone line cannot be used to
ground the air conditioner .
NOTE
3 . Finish wrapping insulating tape around the rest of the pipes leading to the
outdoor unit .
4 . Install a green/yellow coloured grounding wire :
f If the grounding wire is too short, connect an extension lead, in a mechanical way and wrapping it with insulating tape
f
(do not bury the connection) .
f Secure the grounding wire in position with staples .
f
• If the grounding electrode is installed in an area of heavy traffic, its wire must be connected securely .
NOTE
5 . Carefully check the installation, by measuring the grounding resistance with a ground resistance tester . If the resistance is
above required level, drive the electrode deeper into the ground or increase the number of grounding electrodes .
6 . Connect the grounding wire to the electrical component box inside of the outdoor unit .

Testing operations

1 . Check the power supply between the outdoor unit and the auxiliary circuit breaker .
f 1 phase power supply : L1, L2
f
2 . Check the indoor unit .
1) Check that you have connected the power and communication cables correctly . (If the power cable and
communication cables one mixed up or connected incorrectly, the PCB will be damaged . )
2) Check the thermistor sensor, drain pump/hose, and display are connected correctly .
3) KEY buttons are on Main PBA of Outdoor Unit .
28
4way Outdoor_북미향_IM_EN_DB68-05152A-00_CS6.indd 28
Carbon
Steel core
plastic
Terminal M4
To grounding
PVC-insulated green/
screw
yellow wire
1 . 6  ft
1 ft