7.2.3 Configuration of the JBUS/MODBUS communication parameters
Connect the RS232 link
to a terminal
(Microsoft Hyper
terminal)
Use the cord supplied with the card.
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600
baud,
8 bits, no parity, 1 stop bit, and without flow control.
Check that UPS power is on.
Enter the MGEUPS or mgeups password (not modifiable).