The Different Server And Ups Shutdown Sequences; Extended Power Outage, Shutdown Initiated By The Shutdown Timer (Shutdown After); Extended Power Outage, Shutdown Initiated By The "Low Battery Power" Message - MGE UPS Systems 66102 User Manual

Network management card
Hide thumbs Also See for 66102:
Table of Contents

Advertisement

5.1.3.2 Sequential startup
It is possible to delay outlet power-on to reduce inrush currents on startup or to sequence the startup of several
devices.
Controlled outlet startup after a given time is based on startup of the main outlet.

5.2 The different server and UPS shutdown sequences

5.2.1 Extended power outage, shutdown initiated by the Shutdown Timer
(Shutdown after)
During battery backup time, the Shutdown Timer of the Network Management Card is reached: After a user-defined
backup time period
(Shutdown parameters
shutdown (depending on its configuration). The UPS restarts when utility power is restored (depending on its
configuration)
Shutdown duration: Maximum value of shutdown times of the Network Shutdown Modules subscribed to the card. This
value is updated each time a client subscribes/ unsubscribes.
Utility failure
Utility
Main output
NSM 1 on main
output
Output 1
NSM 2 on output 1
5.2.2 Extended power outage, shutdown initiated by the "Low battery power"
message
When the "Low battery power" criterion is displayed, the UPS is shut off after taking into account the shutdown
duration of the servers.
"Low battery power": The message appears if either of the two following criteria is checked:
- Low Battery Level
- Low Battery Delay
ENERGIZE YOUR ENTERPRISE
Network Management Card
– User Manual
page), the shutdown of all servers is initiated, followed by the UPS
Start shutdown main
Start shutdown
output
output 1
Shutdown duration
Shutdown after:
Shutdown after 1:
Shutdown
duration output 1
34003991EN/DA
Utility restore
main output
Page
69/120