Symbol
Name
(function)
Thermistor
TH10
1) Detects the compressor shell
(P-YMF-B
only)
2) Provides compressor shell
THHS
1) Detects the inverter cooling fin
2) Provides inverter overheating
3) Controls the control box cooling
Solenoid
SV1
1) High/low press. bypass at starting/
valve
(discharge -
suction
bypass)
2) Discharge press. rise suppression
SV2
Capacity control and high press. rise
(discharge -
suppression (backup for frequency
suction
control)
bypass)
SV3 ~ 6
Control of heat exchanger capacity.
Linear
SLEV
Adjustment of liquid refrigerant (oil)
expansion
return foam accumulator
valve
LEV1
Adjustment bypass flow rate from
(SC coil)
outdoor unit liquid line at cooling.
Liquid level
CH2, CH3
Heating of refrigerant in accumulator
detection
(accumulator
liquid level detection circuit
heater
liquid level
detection)
Linear
LEV
1) Adjust superheat of outdoor unit
expansion
valve
2) Adjust subcool of indoor unit heat
Thermistor
TH21
Indoor unit control (thermostat)
(inlet air
temperature)
TH22
1) Indoor unit control (freeze
(piping
temperature)
2) LEV control in heating operation
TH23
LEV control in cooling operation
(gas side
(Superheat detector)
piping
temperature)
Application
temperature.
overheating protection.
temperature.
protection.
fan.
stopping and capacity control at
low load
heat exchanger outlet at cooling.
exchanger at heating.
prevention, hot adjust, etc.)
(Subcool detection)
Specification
R
=7.465kΩ
120
B
=4057
25/120
Rt =
7.465exp
1
1
{4057(
-
)}
273+t
273+120
20˚C : 250kΩ
70˚C : 34kΩ
30˚C : 160kΩ
80˚C : 24kΩ
40˚C : 104kΩ
90˚C : 17.5kΩ
50˚C : 70kΩ
100˚C : 13.0kΩ
60˚C : 48kΩ
110˚C : 9.8kΩ
R
=17kΩ
50
B
=4170
25/50
Rt =
1
17exp{4170(
-
273+50
273+t
-20˚C : 605.0kΩ 50˚C : 17.0kΩ
-10˚C : 323.3kΩ 60˚C : 11.5kΩ
0˚C
: 180.9kΩ 70˚C : 8.0kΩ
10˚C : 105.4kΩ 80˚C : 5.7kΩ
20˚C : 63.8kΩ 90˚C : 4.1kΩ
30˚C : 39.9kΩ 100˚C : 3.0kΩ
40˚C : 25.7kΩ
AC 220~240V
Open at energizing and
close at deenergizing
DC12V stepping motor drive
Valve opening 0~480 pulse
Cord heater : 2kΩ
(1kΩ + 1kΩ)
AC220~240V
20W (10W + 10W)
DC12V
Opening of stepping motor
driving valve
60~2,000 pulses
R
= 15kΩ
0
B
= 3460
0/100
Rt =
1
15exp {3460 (
-
273+t
273+0
0°C
: 15kΩ
10°C : 9.7kΩ
20°C : 6.4kΩ
25°C : 5.3kΩ
30°C : 4.3kΩ
40°C : 3.1kΩ
–76–
Check method
• PUHY-
P200·250
YMF-B
• PURY-
P200·250
YMF-B
• PU(H)Y-
(P)200·250
YMF-B
1
)}
• PURY-
(P)200·250
YMF-B
• Continuity check
by tester
• Temperature of
inlet and outlet.
• PURY-
(P)200·250YMF-B
• PU(H)Y-
(P)200·250YMF-B
• PURY-
(P)200·250YMF-B
• PU(H)Y-
(P)200·250YMF-B
Resistance value
• PU(H)Y-
check
(P)200·250YMF-B
• PURY-
(P)200·250YMF-B
Continuity check
with tester for
white-red-orange
yellow-brown-blue
Resistance value
check
1
)}
Object