Download Print this page

Mitsubishi Electric PUHY-200YMF-B Service Handbook page 166

Advertisement

No
SW1
Item
12345678910
52
0010110000
THHS Data
53
1010110000
HPS Data
54
0110110000
TH7 Data
55
1110110000
56
0001110000
TH9 Data
57
1001110000
TH10 Data
58
0101110000
LPS Data
α OC
59
1101110000
α OC*
60
0011110000
61
1011110000
Accumulator Level
α OC*
62
0111110000
HzAK Increase/
Decrease
63
1111110000
Difference from
Target Tc
(Tcm-Tc)
64
0000001000
Difference from
Target Te
(Tem-Te)
65
1000001000
Tc
66
0100001000
Te
67
1100001000
Tcm
68
0010001000
Tem
69
1010001000
Comp Frequency
70
0110001000
INV Output
Frequency
71
1110001000
AK
72
0001001000
SLEV
73
1001001000
BC Address
74
0101001000
FANCON Output
Value (Toff%)
75
1101001000
DC Trunk Line
Current
76
0011001000
OC Address
77
1011001000
IC1 Address/
Capacity Code
78
0111001000
IC2 Address/
Capacity Code
79
1111001000
IC3 Address/
Capacity Code
80
0000101000
IC4 Address/
Capacity Code
81
1000101000
IC5 Address/
Capacity Code
82
0100101000
IC6 Address/
Capacity Code
LD1
LD2
LD3
1 and 2 below are displayed alternately at every 5 seconds.
1 Accumulator Level: 0~9 ("AL=" is also displayed), 2 α OC*: 0~9.999
∆ Hz
∆ Hz
∆ Hz
0
+
Low
Low
Low
-3 ~ -2
-2 ~ -1
-3 deg.
or lower
deg.
deg.
Low
Low
Low
-3 deg.
-3 ~ -2
-2 ~ -1
or lower
deg.
deg.
0 ~ 99
–164–
Display
LD4
LD5
LD6
LD7
-99.9 ~ 999.9
-99.9 ~ 999.9
0 ~ 9.999
∆ AK
∆ AK
High
High
Stable Region
1~2
2~3
deg.
deg.
Stable Region
High
High
1~2
2~3
deg.
deg.
-99.9 ~ 999.9
0 ~ 9999
-99.9 ~ 999.9
0 ~ 9999
0 ~ 99
for PURY-(P)200·250YMF-B
Remarks
LD8
E*
∆ AK
0
+
High
3 deg or
higher
High
3 deg or
higher
Control Frequency E*
Frequency actually out-
put from the inverter. E*
E*
Displays the FANCON
output value used for
control. E*
(M) Monitored by the
inverter's microcomputer.
E
On the left
(LD1~LD4), the IC
address, and on the
right (LD5~LD8), the
capacity code is
displayed (displayed
alternately every 1
minute).

Advertisement

loading