Checking code
Meaning, detecting method
1111
Low
1. When saturation temperature
pressure
sensor (TH2) or liquid level de-
saturation
tecting temperature sensors
tempera-
(TH3, TH4) detects -40˚C or
ture
less (the first time) during op-
sensor
erations, outdoor unit stops
abnormal-
once, mode is changed to re-
ity (TH2)
start mode after 3 minutes, then
the outdoor unit restarts.
2. When -40˚C or less temp. is
detected again (the second
time) within 30 minutes after
stop of outdoor unit, error stop
is observed with code Nos.
"1111," "1112," or "1113" dis-
played.
3. When -40˚C or less tempera-
ture is detected 30 or more min-
1112
Liquid
utes after stop of outdoor unit,
level
the stop is regarded as the first
detecting
time and the process shown in
tempera-
1. is observed.
ture
sensor
4. 30 minutes after stop of outdoor
abnormal-
unit is intermittent fault check
ity (TH4)
period with LED displayed.
Note:
1. Low press. saturation tem-
perature trouble is not de-
tected for 3 minutes after
compressor start, and finish
of defrosting operations, and
during defrosting operations.
2. In the case of short/open of
TH2~TH4 sensors before
starting of compressor or
within 10 minutes after start-
1113
Liquid
ing of compressor, "1111,"
level
"1112," or "1113" is displayed
detecting
too.
tempera-
ture
sensor
abnormal-
ity (TH3)
Cause
1) Gas leak, Gas shortage.
2) Insufficient load operations.
3) Poor operations of indoor LEV.
4) Poor operations of OC controller
LEV:
Cooling
: LEV1
5) Poor operations of BC controller
LEV:
Cooling-only : LEV3
Cooling-main : LEV1, 2, 3
Heating-only, Heating-main:
LEV3, 4
Defrost
: LEV3
6) Poor operations of BC controller
SVM:
Cooling-only, Defrost
7) Poor operations of BC controller
SVM:
Cooling-only, Cooling-main
8) Poor operations of BC controller
SVB:
Heating-only, Heating-main
9) Solenoid valve trouble (SV3 ~ 6)
(PURY).
Heating-only, Heating-main
10)Setting error of connection address.
11)Poor operations of ball valve.
12)Short cycle of indoor unit.
13)Clogging of indoor unit filter.
14)Fall in air volume caused by dust
on indoor unit fan.
15)Dust on indoor unit heat exchanger.
16)Indoor unit block, Motor trouble.
10)~15) : Fall in low pressure
caused by evaporating capac-
ity in cooling-only cooling-prin-
cipal operation.
17)Short cycle of outdoor unit.
18)Dust on outdoor heat exchanger.
19)Indoor unit fan block, motor trouble,
and poor operations of fan control-
ler.
16)~18) : Fall in low press. caus-
ed by lowered evaporating
capa-city in heating-only heat-
ing-principal operation.
20)Poor operations of solenoid valve
SV2.
Bypass valve (SV2) can not
control low pressure drop.
21)Thermistor trouble (TH2~TH10).
22)Pressure sensor abnormality.
23)Control circuit board thermistor
abnormality and pressure sensor
input circuit abnormality.
24)Poor mounting of thermistor
(TH2~TH10).
* There are not LEV2 and LEV4 on CMB-P-V-E.
–131–
Checking method & Countermeasure
See Refrigerant amount check.
Check operating conditions and opera-
tion status of outdoor unit.
Check operation status by actually per-
forming cooling-only or heating-only
operations.
Cooling-only : indoor LEV
LEV1 (PUHY)
LEV1, 2, 3 (BC)
SVM (BC)
SVA (BC)
Heating-only : indoor LEV
LEV3, 4 (PURY)
(BC)
SVB (BC)
SV3~6 (PURY)
See Trouble check of LEV and sole-
noid valve.
Check address setting of indoor unit
connector.
Confirm that ball valve is fully opened.
Check indoor unit, and take measu-res
to troube.
Check outdoor unit, and take measures
to trouble.
Check outdoor unit fan.
See Trouble check of outdoor unit
fan.
See Trouble check of solenoid valve.
Check resistance of thermistor.
See Trouble check of pressure sen-
sor.
Check inlet temp. and press. of sensor
by LED monitor.