1 LEV
Note 1 :
Symptoms of incorrect connection to BC controller LEV board
LEV No.
1
2
3
4
1)
1
2
3
4
2)
1
2
4
3
3)
1
3
2
4
4)
1
3
4
2
5)
1
4
2
3
6)
1
4
3
2
7)
2
3
1
4
8)
2
3
4
1
9)
2
4
1
3
10)
2
4
3
1
11)
3
4
1
2
12)
3
4
2
1
Improper installation is the same for 1 and 2, so it is omitted here.
Note 2 : Method for checking LEV full open, full closed condition
1 Check LEV full opening (pulse) using the LED monitor display (outdoor controller board SW1).
Full opened: 2000 pulses
Full closed: 60 pulses (LEV 1, 2 may be greater than 60 during full heating operation.)
2 With LEV full opened, check for pressure differential by measuring temperature of piping on both sides.
3 With LEV full closed, check for refrigerant noise.
Note 3 : Use the following table to determine opening due to LEV differential pressure control and superheat
control.
BC controller LEV basic operation characteristics
Region
Failure Mode Operating Mode
Small
LEV1, 2
pulse
Large
Small
LEV3
pulse
Large
Small
LEV4
pulse
Large
* There are not LEV2 and LEV4 on CMB-P-V-E.
Cooling-only
Normal
Insufficient heating
Insufficient cooling, insuf-
SH12 large
ficient heating
SC11 small
SH12 large, SC11 small
SC16 large,
SC16 large,
Branch pipe SC small
Branch piping SC small
Indoor SC large.
Insufficient cooling
Insufficient cooling, insuf-
SH12 small,
ficient heating
SC11 small
SH12 small, SC11 small
SC16 small
SC16 large,
Branch piping SC small
Branch piping SC small
Heating-only
High pressure (PS1) - medium pressure (PS3) is large.
Heating-main
High pressure (PS1) - medium pressure (PS3) is small.
Cooling-main
Cooling-only
SH12 is large.
Cooling-main
Heating-only
High pressure (PS1) - mid pressure (PS3) is small.
Heating-main
Cooling-only
SC16 and SH12 are small.
Cooling-main
Heating-only
High pressure (PS1) - mid pressure (PS3) is large.
Heating-main
Heating-only
SH12 is large.
High pressure (PS1) - mid pressure (PS3) is small.
Heating-main
Cooling-only
SC16 is small.
Cooling-main
Heating-only
High pressure (PS1) - mid pressure (PS3) is large.
Heating-main
Cooling-principal
Heating-only
Insufficient heating,
Comp. frequency low
Low press. low
PHM small
PHM small. Heating
Heating indoor SC small
PHM large
PHM large
* There are not LEV2 and LEV4 on CMB-P-V-E.
Description
–119–
Heating-principal
Insufficient heating,
Comp. frequency low
Low press. low
PHM small
Insufficient cooling
Heating indoor SC small
PHM large
Normal Range
2
2.0 ~ 3.5 kg/cm
G
(0.20~0.34MPa)
SH12<25
2.0 ~ 3.5 kg/cm
2
G
(0.20~0.34MPa)
SC16>6
SH12>5 (V-D type)
SH12>5 (V-E type)
2
2.0 ~ 3.5 kg/cm
G
(0.20~0.34MPa)
SH12<25
2.0 ~ 3.5 kg/cm
2
G
(0.20~0.34MPa)
SC16>6
2
2.0 ~ 3.5 kg/cm
G
(0.20~0.34MPa)