System components
Mixing valve extension board, Part No. 7820 193
Electronics board, Part No. 7829 790
Optolink/emissions test switch board, Part No. 7820 165
Programming unit, Part No. 7823 986
(continued)
The circuit board contains:
Operating status indicator
Fault indicator
Optolink laptop interface
Emissions test switch

Additional information

The board contains the relays for
activating the mixing valve motor
and the heating circuit pump of the
mixing valve circuits M2 and M3.
This is connected to the mixing
valve extension board.
All data are processed and the
outputs (relays) activated.
Emissions test switch for flue gas
measurements with the boiler
operated with constant boiler water
temperature for a short time.
The burner is switched on
(this can be delayed if the system
incorporates a fuel preheater)
all pumps are switched on
the mixing valve remains in its
control mode
the boiler water temperature is
controlled by the adjustable high
limit "R".
The programming unit is inserted in
the control unit.
For setting:
Heating program
Set-point values
Switching times
Heating curve (shift and slope)
Date
Time
Energy saving and party mode
For displaying:
Temperatures
Operating status information
Faults