Viessmann VITOTRONIC 300 GW2 Installation And Service Instructions Manual page 70

Hide thumbs Also See for VITOTRONIC 300 GW2:
Table of Contents

Advertisement

Start-up
Steps
(continued)
9. Match the coding addresses (continued)
70
10. Set the established values in coding
Level 1.
Address Setting of
05
the partial output (see point 8) as a percentage proportion of the
max. output; e.g.
partial output: 170 kW
max. output: 210 kW
170 kW
x100 % = 81 %
210 kW
08
units and tens digits of the maximum output established in point
4: e.g. max. output: 210 kW – here set: 10
09
hundreds digit of the maximum output established in point 4: e.g.
max. output: 210 kW – here set: 2
0A
the basic output (see point 6) as a percentage proportion of the
max. output; e.g.
basic output: 70 kW
max. output: 210 kW
70 kW
x100 % = 33 %
210 kW
15
the operating time in seconds established in point 5
Please note:
You will find details of other possible settings in the sections entitled
"Coding 1" and "Coding 2" (see page 114 and 116).