Coding 2
(continued)
Overview of all codings (continued)
Coding as per
Function
factory setting
Address: Value
67: 40
DHW
68: 8
DHW
69: 7
DHW
70: 0
DHW
71: 0
DHW
72: 0
DHW
73: 0
DHW
75: 0
DHW
76: 0
General
77: 1
General
With Vitosolic:
Third DHW temperature
set-point 40°C/ 104°F
In conjunction with 2 DHW
tank temperature sensors
with the DHW tank loading
system:
Switch-off point of DHW
tank heating at set-point
value x 0.8
In conjunction with 2 DHW
tank temperature sensors
with the DHW tank loading
system:
Switch-off point of DHW
tank heating at set-point
value x 0.7
DHW circulation pump ON
according to preset time
program when DHW heating
is released
DHW circulation pump ON
according to preset time
g
p
program
DHW circulation pump ON
according to preset time
g
p
program
DHW circulation pump ON
according to preset time
program
p g
DHW circulation pump ON
during energy saving mode
according to preset time
program
Without LON communication
module
LON participant number
New coding
Possible change
Address:
Value
67: 0
Without third DHW temperature set-point
67: 1
Setting of a third DHW temperature set-point.
to
Adjustable from 1 to 95°C/ 34 to 203°F as
67: 95
per coding address "56"
68: 2
Factor adjustable from 0.2 to 1
per 1 increment = 0.1
to
68: 10
69: 1
Factor adjustable from 0.1 to 0.9
per 1 increment = 0.1
to
69: 9
70: 1
Output of DHW circulation pump dependent
only on preset time program
71: 1
DHW circulation pump OFF during domestic
hot water heating to the 1st set-point value
71: 2
DHW circulation pump ON during domestic hot
water heating to the 1st set-point value
72: 1
DHW circulation pump OFF during domestic
hot water heating to the 2nd set-point value
72: 2
DHW circulation pump ON during domestic hot
water heating to the 2nd set-point value
73: 1
During the time program for the DHW
to
circulation pump ON for 5 minutes once per
73: 6
hour to ON for 5 minutes 6 times per hour
73: 7
DHW circulation pump ON continuously
75: 1
DHW circulation pump OFF during energy
saving mode
76: 1
With LON communication module; recognized
immediately
77: 1
LON participant number selectable from 1 to
to
99
77: 99
Please note:
Each number may be assigned once only.
Additional information
123