TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
Schematic
Pressure dependent VAV cooling/heating with changeover and reheat: TB7200C5x14(x) floating actuator
Modulating floating VAV Actuator
CHANGEOVER
SENSOR
OVERRIDE
ROOM TEMPERATURE CONTROL
MINIMUM AND MAXIMUM POSITION
ADJUSTED ON THE ACTUATOR
Pressure dependent VAV cooling/heating with changeover and reheat: TB7200F5x14(x) analog actuator
Analog VAV Actuator
CHANGEOVER
SENSOR
OVERRIDE
ROOM TEMPERATURE CONTROL
MINIMUM AND MAXIMUM POSITION
ADJUSTED ON THE ACTUATOR
Heating or cooling hydronic valve control: TB7200C5x14(x) floating actuator
Modulating floating Valve
OVERRIDE
ROOM TEMPERATURE
CONTROL THERMOSTAT
Heating or cooling hydronic valve control: TB7200F5x14(x) analog actuator
Analog valve
OVERRIDE
ROOM TEMPERATURE
CONTROL THERMOSTAT
62-2019—05
BO 5-AUX
BO 5-AUX
UI 3 COS
0 V~ COM
24 V ~ HOT
HEATING
BO 1 OPEN
AND/OR
COOLING
BO 2 CLOSE
AND ON/OFF
DUCT HEATER
M16967
BO 5-AUX
BO 5-AUX
UI 3 COS
0 V~ COM
24 V ~ HOT
HEATING
AND/OR
COOLING
AND ON/OFF
DUCT HEATER
M16967
24 V ~ HOT
BO 1 OPEN
BO 2 CLOSE
HEATING OR
COOLING VALVE
M16968
UI 3 COS
0 V~ COM
24 V ~ HOT
HEATING OR
COOLING VALVE
M16968
Wiring
SUPPLY AIR
TEMPERATURE
SENSOR
AO 1
AO 2
0 TO 10
VDC
SUPPLY AIR
TEMPERATURE
SENSOR
UI 3 COS
0 V~ COM
AO 1
0 TO 10
VDC
8
Mandatory
• Out1Conf = 2.0
• CntrltTyp = Floating
• FL time = as per actuator
If heat/cool auto-changeover
with a local discharge air
temperature sensor set:
• SeqOpera = 2 Cooling with
Reheat
• UI3 = COS
C
1
M16976
Mandatory
• Out1Conf = 2.0
• RA/DA = as per actuator
If heat/cool auto-changeover
with a local discharge air
temperature sensor set:
• SeqOpera = 2 Cooling with
Reheat
• UI3 = COS
C
1
M16979
Mandatory
• Out1Conf = 2.0
• CntrltTyp = Floating
• FL time = as per actuator
If cooling only set:
• SeqOpera = 0 Cooling only
If heating only set:
• SeqOpera = 1 Heating only
M16977
Mandatory
• Out1Conf = 2.0
• RA/DA = as per actuator
If cooling only set:
• SeqOpera = 0 Cooling only
If heating only set:
• SeqOpera = 1 Heating only
M16978
Settings