TB7200 SERIES COMMUNICATING ZONE THERMOSTATS
Configuration
parameters
Universal input no.3
UI3
configuration
Default value = None
Menu scroll
MenuScro
Default value = On = Scroll
active
C or F
Sets the display scale of the
thermostat
Default value =°F
Keypad lockout levels.
Lockout
Default value = 0 No lock
Level
Out1Conf
Output # 1 configuration
Default value = 4.0 (2 control
outputs, no changeover)
Control type for Triac models
CntrlTyp
Default value = Floating
62-2019—05
Table 8. Configuration Parameters (Continued)
Default value
Table 9. Keypad Lockout Levels
Occupied Temperature Setpoints
Yes access
0
Yes access
1
Level not used
2
Level not used
3
No access
4
No access
5
Significance and adjustments
(None): No function will be associated with the input
(COC/NH) Change over dry contact. Normally Heat: Used when
both heating and cooling are controlled from the same thermostat
output. Contact closes when cold air/water is present. Only used and
valid if system parameter (Out1Conf) is set at 2.0
(COC/NC) Change over dry contact. Normally Cool: Used when
both heating and cooling are controlled from the same thermostat
output. Contact closes when hot air/water is present. Only used and
valid if system parameter (Out1Conf) is set at 2.0
(COS) Change over analog sensor: Used where heating and
cooling are controlled from the same output. Temperature in duct/pipe
determines control mode (heat/cool). Only used and valid if system
parameter (Out1Conf) is set at 2.0
(SS) Supply air sensor monitoring: Used for supply air temperature
monitoring.
Only used for network reporting of the supply air temperature.
Has no internal function in the thermostat
Removes the scrolling display and only presents the room
temperature to the user. With this option enabled, no status is given of
mode, schedule and outdoor temperature. Outdoor temperature only
displays if a network variable is received.
On = Scroll active
Off = Scroll not active
°F for Fahrenheit scale
°C for Celsius scale
See Table 9 for Lockout level details
Defines the type of operation needed for Output #1 (BO1 and BO2)
2.0, will limit the number of sequences of operation available from 0 to
3
Will enable heat/cool operation from the same output (refer to wiring
diagram)
4.0, can access all the sequences of operation from 0 to 5
Will enable heat/cool operation from different output (refer to wiring
diagram)
Defines the type of control output for the type of valves installed
TB7200C5014x only
On/Off is for normally opened or normally closed 24 Vac 2 position
valves
Floating is for modulating 3 wires control of 24 Vac floating valves
14
Unoccupied Override
Yes access
No access
Yes access
No access