16.5.21 Output Over Current Detection (F23)
Malfunction Decision Conditions:
During operation of cooling and heating, when outdoor DC current is above 40.1 ± 5.0A (for: UD07~09CE) OR
44.7 ± 5.0A (for:UD12~16CE) is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main).
Malfunction Caused:
1
Faulty outdoor unit PCB (main).
2
Faulty compressor.
Abnormality Judgment:
Continue for 7 times.
104