Panasonic WH-MDC09C3E8 Service Manual page 103

Hide thumbs Also See for WH-MDC09C3E8:
Table of Contents

Advertisement

16.5.20 IPM Overheating (F22)
Malfunction Decision Conditions:
During operation of cooling and heating, when temperature 95°C is detected by the outdoor IPM temperature
sensor.
Malfunction Caused:
1
Faulty outdoor unit fan motor.
2
Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue 3 times in 30 minutes.
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents