Status Indicators And Alarms - ICT ICT1500-12SW Instruction Manual

Ict1500 sine wave series
Hide thumbs Also See for ICT1500-12SW:
Table of Contents

Advertisement

AC Outlets:
2 x NEMA 5-15R (115V)
Or 1 x IEC type I (230V)

Status Indicators and Alarms

The 3 LEDs on the front panel and the Form-C alarm contacts on the back
indicate the status of the inverter:
Alarm or
Notification
Inverter AC
Output OK
(Battery Backup
Mode)
External AC
Voltage OK
DC Undervoltage
Warning
Remote
Shutdown
System Fault
DC Undervoltage
Inverter On/Off Switch
Green AC Indicator
- Inverter on (flash)
- Grid power (continuous)
Figure 5: Front Panel
Trigger Condition
Normal operation,
output above 90VAC
(or 180Vac, 230V
models)
AC input (Transfer
Relay option only) is
above set limit, and is
powering the output
Triggers when Input
Voltage drops below
11.0/22.0/44.0VDC for
1 s. Clears when input
is above 11.2/ 22.4/
44.8V for 1s.
Triggers when Remote
Shutdown is activated
over optional Ethernet,
or remote panel switch
Indicates internal
circuit fault - Clears
when all fault
conditions are cleared.
Triggers when Input
Innovative Circuit Technology Ltd.
Yellow - Low Battery
Warning
Inverter
Red
Output
FAULT
LED
Enabled
-
Enabled
-
Enabled
-
OFF
BLINK
OFF
ON
OFF
ON
Red - Fault
Yellow
Green
WARN
AC
LED
LED
-
BLINK
-
ON
ON
-
-
OFF
-
OFF
-
OFF
9