Objects (Modbus-Tcp) Supported Function Code - LG BNU-BAC Installation & Owner's Manual

Hide thumbs Also See for BNU-BAC:
Table of Contents

Advertisement

Objects (Modbus-TCP)
Objects (Modbus-TCP)
Supported Function Code
Monitoring and controlling items of air conditioners supported are assigned with general function
codes specified by Modbus-TCP.
Function Name
Read Coil Status
Read Holding Registers
Force Single Coil
Preset Single Registers
64 Modbus
Code
Run/Stop(status), Lock(status), Swing(status), Alarm, Filter
01h
Sign(status), Mode Lock(status), Wind Flow Lock(status)
Operation Mode(status), Fan Speed(status),
Room Temperature, Error Code,
Set Room Temperature(status),
03h
Set Lower Temperature(status),
Set Upper Temperature(status),
User Mode(status)
Run/Stop(setting), Lock(setting), Swing(setting),
05h
Filter Sign Reset, Mode Lock(setting),
Wind Flow Lock(setting)
Operation Mode(setting), Fan Speed(setting),
Set Room Temperature(setting),
06h
Set Lower Temperature(setting),
Set Upper Temperature(setting),
User Mode(setting)
Description

Advertisement

Table of Contents
loading

Table of Contents