5. SPECIFICATIONS OF ELECTRICAL PARTS

5.1
RAV-363A8-PE
No.
Parts Name
1
Compressor
2
Outdoor unit fan motor
Running capacitor for
3
outdoor fan motor
4
Magnetic contactor
Pressure switch
5
(2-stage)
6
Bimetal Thermostat
7
Crankcase heater
8
Fuse
9
Reverse Phase Protector
5.2
RAV-463A8-PE
No.
Parts Name
1
Compressor
2
Outdoor unit fan motor
Running capacitor for
3
outdoor fan motor
4
Magnetic contactor
Pressure switch
5
(2-stage)
6
Bimetal Thermostat
7
Crankcase heater
8
Fuse
9
Reverse Phase Protector
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Type
Output (Rated) 3.0kW, 2 pole, 3 phase, 380/415V, 50 Hz
ZR49K3-TFD
Winding resistance 3.73 Ω , at 20 °C
SMF-230-63N-3
Output (Rated) 63W, 6 pole,1 phase, 230V, 50 Hz
SMF-230-39N-3
Output (Rated) 39W, 6 pole,1 phase, 230V, 50 Hz
EEP2G405HQA114
AC 400V, 4 µF
FMCa-1S
AC 230V, 50Hz,
Tripping pressure 19 kg/cm
STB-X602
Resetting pressure 13 kg/cm
Tripping temperature 135
CS-7
Resetting temperature 110
AC 240V, 28W
T5A
STR-4AB
Type
Output (Rated) 3.75kW, 2 pole, 3 phase, 380/415V, 50 Hz
ZR61K3-TFD
Winding resistance 2.91 Ω , at 20 °C
SMF-230-63N-3
Output (Rated) 63W, 6 pole,1 phase, 230V, 50 Hz
SMF-230-39N-3
Output (Rated) 39W, 6 pole,1 phase, 230V, 50 Hz
EEP2G405HQA114
AC 400V, 4 µF
FMCa-1S
AC 230V, 50Hz,
Tripping pressure 19 kg/cm
STB-X602
Resetting pressure 13 kg/cm
Tripping temperature 135
CS-7
Resetting temperature 110
AC 240V, 28W
T5A
STR-4AB
- 9 -
www.heronhill.co.uk
Specifications
2
G, 21 kg/cm
2
G
2
2
G, 15 kg/cm
G
0
C
0
C
Specifications
2
G, 21 kg/cm
2
G
2
2
G, 15 kg/cm
G
0
C
0
C
Fax: 01823 665807