Trane SENS-IN-1D18-HD60D29-4 Installer's Manual page 10

Programmable zone sensor for constant volume (cv)
Table of Contents

Advertisement

Option
Function
1
Morning warm-up
2
Economizer minimum
position override
3
Temperature Scale
4
Supply Air Tempering
5
Time Clock
6
Smart Fan
7
Intelligent
Temperature
Recovery
8
Programmable
0 = 7 days (M, T, W, T, F,
Days/Week
9
Programmable
Periods/Day
10
Programmable Fan
Operation
11
Remote Sensor
Installed
12
Check Filter Interval
13
Display Zone
Temperature
14
Keypad Lockout
Enabled
15
Default Temporary
Override Time
16
Buzzer Options
1 = Key Press and Check
Filter, and System Failure
17
Zone Temperature
Calibration
18
Baud Rate
19
CV or HP Operation
20
Default Cooling Set
Point
21
Default Heating Set
Point
22
Minimum Cooling Set
Point
23
Maximum Heating Set
Point
Programming And Operation
Option Value
Default
0 = Disabled
0
1 = Enabled
0 = Disabled
1
1 = Enabled
0 = Fahrenheit
0
1 = Centigrade
0 = Disabled
0
1 = Enabled
0 = 12 hour
0
1 = 24 hour
0 = Disabled
1
1 = Enabled
0 = Disabled
0
1 = Enabled
0
S, S)
1 = 3 days (M-F, S, S)
2 = 2 days (M-F, S-S)
3 = 1 day (Sun-Sat)
2, 3, 4
4
0 = Disallowed
0
1 = Allowed
0 = No
0
1 = Yes
0 = Disabled
350
3000 to 50 in 50 hour
increments
0 = No
1
1 = Yes
0 = Disabled
1
1 = Enabled
1, 2, 3, 4, 5
3
0 = Key Press Only
1
Filter
2 = Key Press, Check
Zone Tempersture
0 offset This allows for field calibration in 0.1 degree increments
Displayed
0 = 1024 baud
1
1 = 1200 baud
0 = CV
0
1 = HP
45 to 98
74
43 to 96
68
45 to 98
45
43 to 96
96
10
Description
When enabled, Heat is turned on if the Zone
temperature is 2 degrees below the heat set point
temperature when the program switches from
unoccupied to occupied. The heat will terminate after 60
minutes regardless if the set point has been reached.
When enabled, the minimum position of the economizer
damper is overridden during the unoccupied period.
Displays the temperature in the selected format.
When enabled, sends the tempering signal to the UCP.
Sets Clock to 12 hour format with AM and PM or 24 hour
military time.
When enabled, the supply fan operates in the AUTO
mode during unoccupied periods regardless of FAN
setting.
When enabled, offsets the set point temperature and
starts the system before the scheduled occupied period
to efficiently reach the occupied temperature set point.
The time is calculated based on a recovery rate of 6
degrees per hour. If option 19 is set for HP, this option is
disabled during EMERgency heat operation.
0 allows all 7 days to be individually programmed. 1
allows Mon - Fri, Sat & Sun to be programmed
separately. 2 allows Mon - Fri and Sat - Sun to be
programmed the same. 3 uses the same program for
each day of the week
If 2 is selected, only Day and Nite periods can be
programmed. If 3 is selected, Morn, Day, and Nite can
be programmed. If 4 is selected, Morn, Day, Eve, and
Nite can be programmed.
If allowed, Supply Fan operation can be programmed for
On or Auto operation for each programmed period.
Determines which source will supply the Room
Temperature input for display.
Adjustable in 50 hour increments. The CHECK FILTER
icon will flash when the accumulated run time is greater
than the interval setting.
If ZSM is in a Normal Run State or in Temporary
Override, the zone temperature will be displayed.
When Enabled, Keypad can be locked out.
Sets the default override time in hours.
Buzzer will sound for a 1/2 sec for every minute if option
is set for 1 or 2.
of either the internal sensor on the ZSM or the remote
sensor if used.
Set to Zero for 3 - 25 Ton Voyager Units built before Jan.
1, 1996 that have the original UCP.
This sets the operation MODE for the ZSM. If HP is
selected, EMERgency heat is available.
If no set point has been programmed or the program is
lost, the value set here becomes the operation set point.
If no set point has been programmed or the program is
lost, the value set here becomes the operation set point.
Sets the minimum programmable cooling temperature
set point.
Sets the maximum programmable heating temperature
set point.