Securing Chimney Components; Altering The Fireplace - Quadra-Fire 5100 ACC Installation Manual

51-i acc wood insert automatic combustion control (acc)
Hide thumbs Also See for 5100 ACC:
Table of Contents

Advertisement

5100 I-ACC
Prefabricated Metal Chimney (Cont'd)
Minimum Width of Cavity Opening - Front
Minimum Width of Cavity Opening - Rear
Minimum Height
Minimum Depth from Front to Rear
NOTE: Refer to chimney liner manufacturer for recom-
mendations on supporting the liner. Installation into
fi replaces without a permit will void the listing.
NOTICE: In Canada when using a factory-built chim-
ney it must be safety listed, Type UL103 HT (2100oF)
[1149oC] CLASS "A" or conforming to CAN/ULC-
S629M, STANDARD FOR 650oC FACTORY-BUILT
CHIMNEYS.
WARNING
Fire Risk.
When lining air-cooled factory-built chimneys:.
Run chimney liner approved to UL 1777 Type
HT requirements (2100 degrees F)
Re-install original factory built chimney cap
ONLY
DO NOT block cooling air openings in chimney
Blocking cooling air will overheat the chimney
G. Securing Chimney Components
All joints should be secured with 3 sheet metal screws or
rivets per pipe manufacturers instructions. The sections must
be attached to the insert and to each other with the crimped
(male) end pointing toward the insert. Figure 14.1.
LINER CONNECTOR
CRIMPED
END
TOWARDS
STOVE
Figure 14.1
WARNING
Fire Risk.
Follow venting manufacturer's clearances and
instructions when installing venting system.
14
Inches
Millimeters
29-1/16
738
25-1/2
648
21-1/4
540
17-9/16
446
FLUE
GAS
DIRECTION
7047-910C
H. Altering the Fireplace
The following modifi cations of factory-built fi replaces are
permissible:
The following parts may be removed:
Damper
Ember Catches
Viewing Screen/Curtain
The fi replace must not be altered. Cutting any sheet metal
parts of the fi replace in which the fi replace insert is to be
installed is prohibited per ANSI Z21.88 except that the
damper may be removed to accommodate a direct-connect
starter pipe or chimney liner,
External trim pieces which do not affect the operation of
the fi replace may be removed providing they can be stored
on or within the fi replace for reassembly if the insert is
removed.
The permanent metal warning label provided in the
component pack must be attached to the back of the
fi replace, with screws or nails, stating that the fi replace may
have been altered to accommodate the insert, and must
be returned to original condition for use as a conventional
fi replace.
If the hearth extension is lower than the fi replace opening,
the portion of the insert extending onto the hearth must be
supported.
Manufacturer designed adjustable support kit can be
ordered from your dealer.
Final approval of this installation type is contingent upon
the authority having jurisdiction.
Smoke Shelf or Baffl e
Fire Grate
Doors
August 25, 2014