2-13. Test Run

Using the control unit

(1) Change the indoor control unit switch from
"ON"
"TEST".
(The outdoor unit will not operate for 3 minutes
after the power is turned ON and after operation is
stopped.)
(2) All the indicator lamps blink while the test run is in
progress.
(3) Temperature control is not possible during the test
run.
(4) If correct operation is not possible, the trouble will
be indicated by the indicator lamps. Refer to "Table
of Self Diagnostic Functions and Corrections" and
correct the problem.
(5) After the test is completed, change the control
unit switch from "TEST"
indicator lamps have stopped blinking. (A function is
included which cancels the test run after a 60-minute
timer has elapsed, in order to prevent continuous
test run operation.)
Indoor control unit switch
ON
OFF
TEST
Indicator lamps
OPERATION TIMER
NOTE
This mode places a large load on the devices. Use it
only for performing test runs.
A test run is not possible if the power is turned ON with
the switch in the TEST position.
After the power has been turned ON, change the
switch once to ON or OFF, then switch it back to the
TEST position.
2-14. Precautions
Request that the customer be present when the test
run is performed. At this time, explain the operation
manual and have the customer perform the actual
steps.
Be sure to pass the manuals and warranty certificate to
the customer.
Check that the 220 – 240 V AC wiring is not connected
to the inter-unit control wiring connector terminal.
* If 220 – 240 V AC is accidentally applied, the
indoor or outdoor unit control PCB fuse (0.5 A for
both indoor and outdoor units) will blow in order to
protect the PCB. Correct the wiring connections,
then disconnect the 2P connectors (indoor: blue)
(outdoor: blue, serial 1) that are connected to the
PCB, and replace them with 2P connectors (indoor:
brown) (outdoor: brown, serial 2).
If operation is still not possible after changing the
brown connectors, try cutting the varistor (black)
(both indoor and outdoor).
(Be sure to turn the power OFF before performing
this work.) (Fig. 2-10)
"ON". Confirm that the
STANDBY
2-11
Indoor unit control PCB
2 HP
Varistor (black)
VA002
SW103
2P connector (brown)
2P connector (blue)
3 HP
Outdoor unit control PCB
SPW-C256/366VH
HIC
Temperature
sensor
Up side
C2 (CN020, WHT)
MOV (CN25, WHT)
Bottom
side
SPW-C486VH
F101
MOV
(CN025, WHT)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
SPW-C256/366VH8
System address rotary switch
System address 10s digit and 20s digit
DIP switch
SPW-C486/606VH8
Fuse (0.5A)
CHK (2P plug)
ON
OFF
TEST
Fuse (0.5A)
2P connector (blue)
2P connector (brown)
TEST
SW103
ON
OFF
Varistor (black)
VA002
CHK (2P plug)
AUTO ADD (CN041)
System address
Rotary switch (S002)
TERMINAL (S010)
JP007
System address
DIP switch (S003)
RC-P (CN032,RED)
LED1
LED2
PUMP DOWN (CN042)
EEPROM (IC006)
C1 (CN021, BLK)
TO (CN022, WHT)
TD, TS (CN023, WHT)
EXCT (CN026, RED)
SILENT (CN028, WHT)
RC-P (CN032, RED)
FAN (CN030, WHT)
ROM (CN012, WHT)
OC (CN013, BLU)
EMG (CN014, BRN)
20S (CN09, WHT)
FUSE (25A, F003)
Varistor (VA002)
JP007
Varistor (VA001)
Terminal plug (CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
EEPROM (IC007)
PRY (CN110, YEL)
C2 (CN020, WHT)
C1 (CN021, WHT)
Automatic address
button (black)
Terminal plug (black)
Terminal plug (CN015, BLK)
OC (CN013, BLU)
EMG (CN014, BRN)
JP007
ROM (CN012, WHT)
EEPROM (IC007)
TD (CN024, BLK)
TO (CN023, BLK)
MOV(CN025, WHT)
C2 (CN020, WHT)
C1 (CN021, WHT)
TS (CN022, RED)
Fig. 2-10
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents