1-12. Installation Instructions

Tubing Length

(A) Single type
Keep refrigerant tubing between the indoor and outdoor
units as short as possible.
The length of the refrigerant tubes between the indoor
and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make
both the tubing length (L) and the difference in elevation
(H1) as short as possible.
Single
Main tubing L
(B) Simultaneous operation multi (Twin, Triple, Double-Twin)
NOTE
Because the indoor units run simultaneously, install them within the same room.
Item
Maximum
One-way length of tubing
allowable
from outdoor unit to the most
Allowable
tubing length
distant indoor unit
tubing
Maximum
Maximum length following
lengths
distribution
the fi rst branch point (No. 1
tubing length
distribution)
Difference between the
Maximum branch tubing
maximum length and minimum
length
length in tubing following the
fi rst branch point
Maximum difference between lengths of No. 1 distribution
tubing (double twin)
Maximum difference between lengths of No. 2 distribution
tubing (double twin)
Maximum
If outdoor unit is higher
Maximum
indoor-
allowable
outdoor height
If outdoor unit is lower
height
difference
difference
Maximum height difference between indoor units
* For connection tubing sizes, refer to the table above.
Twin
Main
tubing L
A
Distribution joint
1
2
Distribution joint
(purchase separately)
A = APR-P160BG
B = APR-RTP280AGB
NOTE
For refrigerant tube branches, use the optional distribution joints.
For cautions on the use of the optional distribution joints, be sure to refer to the provided instruction sheet. Also,
be careful to install them in the correct direction (orientation).
Contents
Single
L + ℓ1
L
L + ℓ2
-
ℓ1, ℓ2
ℓ1>ℓ2
-
ℓ1 - ℓ2
-
-
-
Triple
Main
tubing L
B
Distribution tubing
1
3
2
1-321
Table 1-1
Outdoor unit type
Maximum allowable tubing length
Charge-less tubing length
(actual length)
Additional charge per 1 m
Outdoor unit type
Maximum allowable tubing length
Charge-less tubing length
(actual length)
Additional charge per 1 m
Symbol
Twin
Triple
Double-Twin
L + ℓ1, L + ℓ2
L + L1 + ℓ1, L + L1 + ℓ2
L + ℓ3
L + L2 + ℓ3, L + L2 + ℓ4
L1 + ℓ1, L1 + ℓ2
ℓ1, ℓ2, ℓ3
L2 + ℓ3, L2 + ℓ4
ℓ1>ℓ2>ℓ3
Max.: L2 + ℓ2
ℓ1 - ℓ2
Min.: L1 + ℓ1
ℓ1 - ℓ3
(L2 + ℓ4) - (L1 + ℓ4)
ℓ2 - ℓ3
L2 > L1
-
-
L2 - L1
ℓ2 > ℓ1, ℓ4 > ℓ3
-
-
ℓ2 - ℓ1, ℓ4 - ℓ3
H1
H1
H2
H2, H3, H4
H2, H3, H4, H5, H6, H7
Double-Twin
Main
tubing L
L1
A
1
2
Distribution joint
No. 2
25 type
50 m
3 - 20 (30 : VH8) m
40 g
36, 48, 60 types
50 m
5 - 30 m
40 g
Actual length (m)
25
25
single
twin
48,60
≤ 50
≤ 40
-
≤ 15
-
≤ 10
-
-
-
-
≤ 30
≤ 30
≤ 15
≤ 15
-
≤ 0.5
≤ 0.5
A
Distribution joint No. 1
L2
A
3
4
1
36,
≤ 50
≤ 15
≤ 10
≤ 10
≤ 10
≤ 30
≤ 15