To Flush The System; To Use Dry Nitrogen To Flush The System; To Use Refrigerant To Flush The System - Electrolux FPRH17D7KF All Refrigerator Professional Series Servicing

All refrigerator and all freezer professional 17 cu. ft. units with mechanical controls
Table of Contents

Advertisement

Section 4 Refrigeration

To Flush The System

CAUTION
Use extreme care when using Dry Nitrogen to
flush systems. Pressure in nitrogen cylinder
could be as high as 2000 psi. Nitrogen cylinder
must be equipped with approved pressure
regulator and pressure relief valve. Ensure that
your hoses have adequate ratings for pressure
involved and that all of your equipment is in
good condition. The end of the flushing hose
on this tank regulator must be equipped with
a hand shut-off valve (Robinair No. 40380).
Close hand shut-off valve and adjust nitrogen
regulator to correct pressure before proceeding
with flushing procedure.

To Use Dry Nitrogen To Flush The System:

1. Remove compressor and filter-drier. Connect process
coupling to outlet tube of condenser.
2. Fasten cloth over other end of coil to prevent old oil
from spraying over room.
3. Connect hand shut-off valve on flushing hose to
process coupling.
4. Slowly open hand shut-off valve and allow nitrogen
to flow through condenser until discharge is clear.
CAUTION
DO NOT exceed 300 Psi.
5. Disconnect cap tube from evaporator. Flush
evaporator in same manner as condenser.
CAUTION
DO NOT exceed 150 Psi.
6. Flush cap tube. This is only possible if you have
proper service valve adapter.
CAUTION
DO NOT exceed 300 Psi.
7. Reassemble system.
4-4

To Use Refrigerant To Flush The System:

CAUTION
Refrigerant used for flushing must be recovered
into a recovery system. Meter amount of
refrigerant used for flushing with your charging
cylinder. DO NOT OVERFILL THE BAG.
1. Disconnect the suction and discharge lines from the
compressor and remove the filter-drier. Connect
process coupling to outlet and inlet tube of
condenser.
2. Connect hose to outlet process coupling and
charging cylinder. Connect another hose to inlet
coupling and recovery system.
3. Open charging cylinder and allow refrigerant to flow
through condenser until discharge into bag is clear.
NOTE
The line piercing valve (clamp-on type) should be
used for test purposes only. It must be removed from
system after it has served its purpose.
4. Disconnect capillary tube from evaporator. Flush
evaporator in same manner as condenser.
5. Flush cap tube. This is only possible if you have
proper service valve adapter.
6. Reassemble system.