Vent Pipe Clearances - Vermont Castings 300DVBHNV7 Homeowner's Installation And Operating Instructions Manual

Dvbh7 series
Table of Contents

Advertisement

VeNtING INStAllAtIoN
Horizontal sections of this vent system
require a minimum of 3" clearances to
combustibles at the top of the flue and 1"
clearance at the sides and bottom until
the flue penetrates the outside wall. A
minimum 1" clearance all around the flue
is acceptable at this point of penetration. If
vertical rise is 7Z\x" feet or higher when top
venting, the clearance to combustibles is 1"
on all sides of the horizontal run.
Vertical sections of this vent system require
a minimum of 1" clearance to combustibles
on all sides of the pipe.
*3"
Figure 16 -
Combustible Clearances for Vent Pipe
54D8001
**1"
**1"
48"
(1219 mm)***
***44 " (1130 mm)
for 300 Series
FP2586
vent pipe clearance
DVBH7 Series Direct Vent Gas Fireplace
this fireplace must be vented to the outside.
the venting system must NeVeR be attached
to a chimney serving a separate solid fuel
burning appliance. each gas appliance must
use a separate vent system. Do not use
common vent systems.
*3"
* A Minimum 3" Clearance to the Top is
Required Along Horizontal Length until
Flue Pipe Penetrates Outside Wall
** A Minimum 1" Clearance to Combus-
tibles Permitted All Around Flue at Out-
side Wall
**1"
**1"
33 " 
(841 mm)***
***29 " (753 mm) 
for 300 Series
FP095a
15