6.5.2.1 If TA﹥TS+1℃, the outdoor fan operates. After 15 seconds, the compressor operates.
6.5.2.2 The compressor is on, if TA≤TS, this compressor will stop. If the outdoor fan operates for 3
minutes at least, it will stop after delaying for 5 seconds.
6.5.3. When the unit is off, the compressor stops at first, and the indoor/outdoor fan will stop after
delaying for 5seconds.
6.5.4. Power management (for power management models)
Entering into the only-cooling mode, indoor fan motor operates immediately and keeps moving
for 30 minutes at lease. Compressor operates, and indoor fan motor keeps moving; Compressor
stops operation, indoor fan motor shuts off after a delay of 30 minutes.
6.5.5. The ION/TIMER functions are valid at the cooling mode.

6.6 Drying mode

6.6.1. The unit operates at drying mode. If TA>13℃, outdoor fan turns on, and then the compressor
operates after 15 seconds later.
Operation conditon
(TA-Ts) ℃
+1
0
Compressor off
Operation conditon
TA ℃
15
13
Compressor off
Compressor on
Compressor on
12