OPERATION AND DIAGNOSTIC
LIGHTS
The diagnostic control panel has up to 6 indicating and
diagnostic lights to show all major steps of operation and
control sensed malfunctions. This panel is located on the left
end of the unit.
TABLE - O
Status LED Diagnostic Codes
Code Sequence
Constant ON
System OK, no faults present.
Constant OFF
Possible control fault, check power;
LED may be effective, do not replace
control if all operational sequences
function properly, see Trouble Shooting
Guide.
Low Air, check air pressure switch and
One Flash
hoses to pressure sensing points, fan,
venting and sealing of pressurized
chamber. Note:Brief flashing normal on
fan start-up/proving.
Two Flashes
Flame without call for heat, check for a
gas valve stuck in the open position, air,
venting, burners and the combustion
process. Fan will remain on.
Three Flashes
Lockout due to flame failure, push reset
button on inner control panel after
correcting ignition problem. Initial heater
start up without properly bleeding air
from the gas line may require multiple
reset functions to achieve proper ignition.
Igniter failure, igniter will not maintain
Four Flashes
minimum 2.75 amp current draw, caused
by, low voltage, bad wiring/continuity,
high resistance or igniter failure.
Power supply problem, check for low
Five Flashes
supply voltage or transformer output less
than 18VAC.
Replace ignition module, internal
Six Flashes
fault.
TA
Condition
Installation and
Service Manual
Status LED Diagnostic Codes
Code
Sequence
Prepurge
Trial for Ignition
Stage 1 On
Stage 2 On
(985,000 - 2,065,000 Btu/hr)
Status
Alarm
Figure 40 - Operation/Diagnostic Lights
35
TABLE - P
Condition Lights
Operation of combustion
air fan before ignition on
stages 1 and 2.
Hot surface igniter
preparing to light burners.
Burners for stage 1 operating.
Burners for stage 2 operating.
Remote status light for
ignition module.
Indicates flame failure on
the ignition module and
will indicate additional
alarms if the alarm of any
failure option is purchased.
Models 495,000 - 745,000 Btu/hr
Models 985,000 - 2,065,000 Btu/hr