Mitsubishi Electric PUHZ-P200YHA Service Manual page 9

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P200YHA:
Table of Contents

Advertisement

6-4. STANDARD OPERATION DATA
Representative matching
Mode
Capacity
Input
Indoor unit
Phase , Hz
Voltage
Input
Current
Outdoor unit
Phase , Hz
Voltage
Current
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
SHF
BF
The unit of pressure has been changed to MPa based on international SI system.
The conversion factor is: 1(MPa)=10.2(kgf/cm²)
OCH424E
PEA-RP200GA
Cooling
W
19,000
kW
7.21
PEA-RP200GA
V
kW
A
PUHZ-P200YHA
PUHZ-P200YHA3
PUHZ-P200YHA3R1/R2/R3
V
9.47
A
MPa
2.96
(30.2)
(kgf/
)
0.87
MPa
(8.87)
(kgf/
)
75.6
°C
49.7
°C
8.0
°C
7.5
m
D.B.
27
°C
W.B.
19
°C
D.B.
17.1
°C
D.B.
35
°C
W.B.
24
°C
0.81
0.18
9
Heating
22,400
7.36
3, 50
400
1.00
2.00
3, 50
400
9.88
2.59
(26.4)
0.64
(6.53)
73.7
43.2
-0.8
7.5
20
15
35.7
7
6
PEA-RP250GA
Cooling
Heating
22,000
27,000
8.44
8.47
PEA-RP250GA
3, 50
400
1.18
2.30
PUHZ-P250YHA
PUHZ-P250YHA3
PUHZ-P250YHA3R1/R2/R3
3, 50
400
11.0
12.0
2.94
2.67
(30.0)
(27.2)
0.86
0.62
(8.75)
(6.32)
74.8
74.0
49.6
45.1
7.1
-2.3
7.5
7.5
27
20
19
15
15.4
39.1
35
7
24
6
0.86
0.15

Hide quick links: