Mitsubishi Electric PUHZ-P200YHA Service Manual page 65

Split-type, heat pump air conditioners
Hide thumbs Also See for PUHZ-P200YHA:
Table of Contents

Advertisement

SW2 setting
Indoor setting temperature
ON
17~30
1
2 3 4 5 6
Outdoor pipe temperature/Cond./Eva.
ON
(TH6)
-39~88
1
2 3 4 5 6
Outdoor outside temperature (TH7)
-39~88
ON
1
2 3 4 5 6
Outdoor heatsink temperature (TH8)
-40~200
ON
1
2 3 4 5 6
Discharge superheat SHd
0~255
ON
Cooling = TH4-TH6
1
2 3 4 5 6
Heating = TH4-TH5
Subcool SC
0~130
Cooling = TH6-TH3
Heating = TH5-TH2
ON
<From 17U***** (unit No.) onward>
Number of defrost cycles
1
2 3 4 5 6
0 – FFFE
Input current of outdoor unit
ON
1
2 3 4 5 6
U9 Error status
ON
1
2 3 4 5 6
DC bus voltage
ON
300-750
1
2 3 4 5 6
OCH424E
Display detail
65
The black square (■) indicates a switch position.
Explanation for display
17~30
-39~88
(When the temperature is 0: or less, "–" and tem-
perature are displayed by turns.)
-39~88
(When the temperature is 0: or less, "–" and tem-
perature are displayed by turns.)
-40~200
(When the temperature is 0: or less, "–" and tem-
perature are displayed by turns.)
(When the thermistor detects 100: or more, hun-
dreds digit, tens digit and ones digit are displayed by
turns.)
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0 – FFFE (in hexadecimal notation)
(When more than FF in hex (255 in decimal), the
number is displayed in order of 16
1
0
16
's and 16
's places.
(Example) When 5000 cycles;
0.5 secs.
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
Description
Normal
Overvoltage error
Undervoltage error
Input current sensor error
L
-phase open error
1
Abnormal power synchronous signal
Display examples for multiple errors:
Overvoltage (01) + Undervoltage (02) = 03
Undervoltage (02) + Power-sync signal error (08) = 0A
300-750
(When it is 100V or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
3
's and 16
2
's, and
0.5 secs.
2 secs.
9
C4
Detection point
Display
00
Power circuit board
01
Power circuit board
02
Controller circuit board
04
Power circuit board
08
Unit
:
:
:
:
°C
°C
2 cycles
0.1 A
Code