Abnormal point and detection method
Error Code
Open/short of outdoor unit thermistors
(TH3, TH6, TH7, and TH8)
Abnormal if open or short is detected
during compressor operation.
Open detection of thermistors TH3 and
TH6 are inoperative for 10 seconds to 10
minutes after compressor starting and 10
minutes after and during defrosting.
WCheck which unit has abnormality in its
thermistor by switching the mode of SW2.
(PAC-SK52ST)
(Refer to 11-10.)
WHeatsink thermistor (TH8) is in the power
module.
U4
(TH3: 5105)
(TH6: 5107)
(TH7: 5106)
(TH8: 5110)
Symbol Name
Thermistor <Outdoor pipe>
TH3
Thermistor <Outdoor 2-phase pipe>
TH6
Thermistor <Outdoor>
TH7
TH8
Thermistor <Heatsink>
Temperature of heatsink
Abnormal if heatsink thermistor (TH8)
detects temperature 95:.
w Heatsink thermistor is in the power mod-
ule.
U5
(4230)
Power module
Check abnormality by driving power module
in case overcurrent is detected.
(UF or UP error condition)
U6
(4250)
Outdoor fan motor
Abnormal if rotational frequency of the fan
motor is not detected during DC fan motor
operation.
Fan motor rotational frequency is abnormal if;
U8
• 100 rpm or below detected continuously
(4400)
for 15 seconds at 20: or more outside
air temperature.
• 50 rpm or below or 1500 rpm or more
detected continuously for 1 minute.
OCH424E
1 Disconnection or contact failure
of connectors
Outdoor controller circuit
(
board: TH3,TH7/6
2 Defective thermistor
3 Defective outdoor controller
circuit board
4 Defective outdoor power circuit
board (TH8 open/short)
Thermistors
1 The outdoor fan motor is
locked.
2 Failure of outdoor fan motor
3 Air flow path is clogged.
4 Rise of ambient temperature
5 Defective thermistor
6 Defective input circuit of
outdoor power circuit board
7 Failure of outdoor fan drive circuit
1 Outdoor stop valve is closed.
2 Decrease of power supply voltage
3 Looseness, disconnection or
converse of compressor wiring
connection
4 Defective compressor
5 Defective outdoor power circuit
board
1 Failure in the operation of the
DC fan motor
2 Failure in the outdoor circuit
controller board
Case
1 Check connection of connector (TH3,TH7/6) on
the outdoor controller circuit board.
)
Check breaking of the lead wire for thermistor
(TH3,TH6,TH7). Refer to 11-9.
2 Check resistance value of thermistor
(TH3,TH6,TH7) or check temperature by
microprocessor.
(Thermistor/TH3,TH6,TH7 : Refer to 11-6.)
(SW2 on A-Control Service Tool:
Refer to 11-10.)
3 Replace outdoor controller circuit board.
4 Replace outdoor power circuit board.
WEmergency operation is available in case of
abnormalities of TH3, TH6 and TH7.
Refer to 11-8.
Open detection
– 40
or below
– 40
or below
– 40
or below
– 35
or below
12 Check outdoor fan.
3 Check air flow path for cooling.
4 Check if there is something which causes
temperature rise around outdoor unit.
(Upper limit of ambient temperature is 46:.)
Turn off power, and on again to check if U5
is displayed within 30 minutes.
If U4 is displayed instead of U5, follow the
action to be taken for U4.
5 Check resistance value of thermistor (TH8)
or temperature by microprocessor.
(Thermistor/TH8: Refer to 11-6.)
(SW2 on A-Control Service Tool: Refer to
11-10.)
6 Replace outdoor power circuit board.
7 Replace outdoor controller circuit board.
1 Open stop valve.
2 Check facility of power supply.
3 Correct the wiring (U·V·W phase) to
compressor. Refer to 11-9 (Outdoor power
circuit board).
4 Check compressor referring to 11-6.
5 Replace outdoor power circuit board.
1 Check or replace the DC fan motor.
2 Check the voltage of the outdoor circuit
controller board during operation.
3 Replace the outdoor circuit controller board.
(When the failure is still indicated even after
performing the remedy 1 above.)
30
Judgment and action
Short detection
90
or above
90
or above
90
or above
170 or above