13.2. Display functions

13.2.1. Flow temperature setpoint

Siemens Building Technologies
Landis & Staefa Division
Displayed is the current flow temperature setpoint which is composed of the following
variables:
Flow temperature setpoint in function of the composite outside temperature and the
heating curve
Position of the setting knob for room temperature readjustments
Parallel displacement of heating curve (setting on operating line 72)
With demand-compensated control (plant types 4, 5 and 6), the display shows --- .
Generation of flow temperature setpoint:
Heating curve
T
V
T
VS
T
, composite
AM
outside
temperature
s
Slope
T
Composite outside temperature
AM
T
Flow temperature setpoint (generated via the heating curve)
VS
T
Flow temperature setpoint
V
Basic Documentation RVL470
Function block "Service functions and general settings"
Parallel displacement of
heating curve, operating line 72
1 + s
T
T
VS
V
s
T
AM
1 + s
Knob on
controller
Flow temperature setpoint
operating line 165
CE1P2522E / 30.03.2000
43/68