Application Individual room temperature control in HVAC installations that are heated or cooled. Controlling these types of equipment: • Valve actuators • Air damper actuators Product Number RCU61U With three-position signal for heating, without operating mode selector Siemens Industry, Inc.
Page 2
When used in connection with a VAV controller, this setting must be taken into account. To set minimum limitation, use a screwdriver to adjust the potentiometer (see Figure 2). Values on the scale are percentage of full operation. Page 2 Siemens Industry, Inc.
Page 3
To set limit stops, remove the setpoint knob by pulling it straight off the shaft. Reposition gray tabs for high and low stops in the holes around the perimeter of knob as required. See Figure 4. Figure 4. Setpoint Limit Stops. Siemens Industry, Inc. Page 3...
The screw terminals are mounted on the base. The DIP switches and the potentiometer are located at the rear of the unit. To access the DIP switches, remove the controller from the controller base. See Figure 5. Figure 5. DIP Switch Settings. Page 4 Siemens Industry, Inc.
Page 5
Mounting height is approximately 47 inches (120 cm) above the floor. See Figure 6. • The connecting wires can be run to the controller from a recessed conduit box. • Only authorized personnel should open the controller. Figure 6. Acceptable Mounting Height. Siemens Industry, Inc. Page 5...
Page 6
10. Pull the wiring through the controller base. 11. Position the controller housing over the two mounting lugs located at the top of the controller base, and press down on the cover until the bottom lugs snap in place. Page 6 Siemens Industry, Inc.
Page 7
12. Terminate the wires per wiring instructions located above the terminal block. Continued Figure 8. Wiring Termination. 13. Reattach the controller to the controller base. Figure 9. Controller Reattachment. 14. Adjust the setpoint dial to the desired setting. The installation is now complete. Siemens Industry, Inc. Page 7...
Page 8
8. Follow Drywall Mounting Steps 6 through 14. The installation is now complete. Figure 10. 4 × 4-inch Electrical Wall Box Installation. Electrical wall box Adapter mask * Plaster ring Controller base Wall box adapter * Controller * Included with ARG70 Page 8 Siemens Industry, Inc.
Page 9
7. Follow Drywall Mounting, Steps 6 through 14. The installation is now complete. Figure 11. 2 × 4-inch Electrical Wall Box Installation. Electrical wall box Controller base Wall box adapter * Controller Adapter mask * * Included with ARG70 Siemens Industry, Inc. Page 9...
C22.2 No. 24-93 Connection terminals 2 × 16 AWG or 1 × 14 AWG General Maximum 20 AWG Use solid wires or prepared stranded wires. Weight 0.5 lb (0.23 kg) Housing color Cover White Base Gray Page 10 Siemens Industry, Inc.