Function Block "Service Functions And General Settings; Operating Lines - Siemens RVL470 Basic Documentation

Heating controllers
Table of Contents

Advertisement

13. Function block "Service functions and general
settings"

13.1. Operating lines

CE1P2522E / 30.03.2000
42/68
Function block "Service functions and general settings" is used to combine various dis-
plays and setting functions that are of assistance in connection with commissioning and
service work. In addition, a number of extra functions are performed.
The service functions are independent of the type of plant. Function block Service func-
tions and general settings
Line
Function, parameter
161
Outside temperature simulation
162
Relay test
163
Sensor test
164
Test of H-contacts
165
Flow temperature setpoint
Resulting heating curve
166
167
Outside temp. for frost protection for the plant
168
Flow temp. setpoint for frost protection for the plant
169
Device number
170
Segment number
Flow alarm
171
172
Operating mode when terminals H1-M are bridged
173
Amplification of locking signal
174
Pump overrun time
175
Periodic pump run (pump kick)
176
Winter- / summertime changeover
177
Summer- / wintertime changeover
178
Clock operation
179
Bus power supply
180
Outside temperature source
Basic Documentation RVL470

Function block "Service functions and general settings"

Unit
Factory
Range
setting
--.- / −50...+50
°C
--.-
0
Display function
Display function
Display function
Display function
°C
2.0
--.- / 0...25
°C
15
0...140
0
0...16
0
0...14
hh:mm
--:--
--:-- / 1:00...10:00
0
%
100
0...200
min
6
0...40
0
dd:MM
25.03
01.01. ... 31.12
dd:MM
25.10
01.01. ... 31.12
0
A
0 / A
A
A / 00.01...14.16
Siemens Building Technologies
Landis & Staefa Division
0...4
0...3
0/1
0...3