Table of Contents

Advertisement

3. DRY operation

Note8. When room temperature is 18°C or below, the compressor can not turn ON. When the room temperature rises to
18°C or above, the compressor will start operation after a 3-minute time delay.
Note9. Refer to page 23 for the compressor operation time.
Note10. In DRY operation, the indoor fan runs on the low speed during the compressor ON and stops during the compressor
OFF.
Dry operation
<Note 8>
Room
YES
temperature
18°C or below
NO
NO
Compressor ON
YES
NO
Compressor ON
3 min. elapse
YES
<Note 5>
NO
Compressor
thermostat ON
YES
NO
Compressor ON
time completed
YES
Compressor OFF
10-minute timer start
Compressor OFF
<Note 10>
Fan stop
1
19
YES
Compressor ON
3 min. delay
NO
<Note 5>
YES
Compressor
thermostat ON
NO
Compressor OFF
10 minutes completed
YES
<Note 9>
Compressor ON
time set
YES
Compressor ON
<Note 10>
Fan speed LOW