Napoleon GD36NTR Installation And Operating Instructions Manual page 51

Table of Contents

Advertisement

SYMPTOM
Pilot goes out while
standing; Main burner is in
'OFF' position.
Flames are consistently
too large or too small.
Carboning occurs.
Flames are very aggressive.
Main burner fl ame is a
blue, lazy, transparent
fl ame.
Carbon is being
deposited on glass, logs
or combustion chamber
surfaces.
White / grey fi lm forms.
Exhaust fumes smelled in
room, headaches.
Remote wall switch is in
'OFF' position; main burner
comes on when gas knob
is turned to 'ON' position.
PROBLEM
Gas piping is undersized.
Unit is over-fi red or underfi red.
B
A
Door is ajar.
Blockage in vent.
Incorrect installation.
Air shutter has become
blocked.
Flame is impinging on the logs
or combustion chamber.
Sulphur from fuel is being
deposited on glass, logs or
combustion chamber surfaces.
Appliance is spilling.
Wall switch is mounted upside
down.
Remote wall switch is
grounding.
Remote wall switch wire is
grounding.
Faulty valve.
TEST SOLUTION
-
Turn on all gas appliances and see if pilot fl ame fl utters,
diminishes or extinguishes, especially when main burner
ignites. Monitor appliance supply working pressure.
-
Check if supply piping size is to code. Correct all
undersized piping.
-
Check pressure readings:
-
Inlet pressure can be checked by turning screw (A)
counter-clockwise 2 or 3 turns and then placing pressure
gauge tubing over the test point. Gauge should read
7" (minimum 4.5") water column for natural gas or 13"
(minimum 11") water column for propane. Check that
main burner is operating on 'HI'.
-
Outlet pressure can be checked the same as above
using screw (B). Gauge should read 3.5" water column
for natural gas or 10" water column for propane. Check
that main burner is operating on 'HI'.
-
AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL.
DO NOT OVER TORQUE.
-
Leak test with a soap and water solution.
-
Tighten screws holding door in place.
-
Remove blockage. In really cold conditions, ice buildup
may occur on the terminal and should be removed as
required.
-
Refer to Figure 31 to ensure correct location of storm
collars.
-
Ensure air shutter opening is free of lint or other
obstructions.
-
Check that the logs are correctly positioned.
-
Open air shutter to increase the primary air.
-
Check the input rate: check the manifold pressure and
orifi ce size as specifi ed by the rating plate values.
-
Check that the door gasketing is not broken or missing
and that the seal is tight.
-
Check that both vent liners are free of holes and well
sealed at all joints.
-
Check that minimum rise per foot has been adhered to
for any horizontal venting.
-
Clean the glass with a recommended gas appliance
glass cleaner.
-
DO NOT CLEAN GLASS WHEN HOT.
-
If deposits are not cleaned off regularly, the glass may
become permanently marked.
-
Ensure exhaust bracket gasket seal.
-
Check door seal and relief fl ap seal.
-
Check for chimney blockage.
-
Check that chimney is installed to building code.
-
Room is in negative pressure; increase fresh air supply.
-
Check cap gasket on the fl ue pipe assembly.
-
Reverse.
-
Replace.
-
Check for ground (short); repair ground or replace wire.
-
Replace.
51
42.3_2
W415-0773 / 06.16.09