Do not use this furnace during construction when adhesives,
sealers, and/or new carpets are being installed and curing. If
the furnace is required during construction, use clean outside
air for combustion and ventilation. Compounds of chlorine
and fluorine, when burned in combustion air, form acids
which will cause corrosion of the heat exchangers and metal
vent system. Some of these compounds are released from
paneling and dry wall adhesives, paints, thinners, masonry
cleaning materials, and many other solvents commonly used
in the construction process.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
This furnace must be installed so the electrical components are
protected from water.
Locate the furnace as near the center of the air distribution system
and chimney or vent as possible. The furnace should be installed
as level as possible. When a furnace is installed so that the supply
ducts carry air to areas outside the space containing the furnace,
the return air must also be handled by a duct(s) sealed to the
furnace casing and terminating outside the space containing the
furnace.
Provide ample space for servicing and cleaning. Always comply
with the minimum fire protection clearances shown on the unit
clearance label. This furnace shall not be installed directly on
carpeting, tile, or any combustible material other than wood
flooring.

LOCATION RELATIVE TO COOLING EQUIPMENT

The cooling coil must be installed parallel with or on the
downstream side of the furnace to avoid condensation in the heat
exchangers. When installed parallel with a furnace, dampers or
other means used to control the flow of air must prevent chilled air
from entering the furnace. If the dampers are manually operated,
they must be equipped with means to prevent operation of either
unit unless the damper is in the full-heat or full-cool position.

HAZARDOUS LOCATIONS

When the furnace is installed in a residential garage, it must be
installed so that the burners and ignition source are located at least
18 in. above the floor. The furnace should be protected from
physical damage by vehicles. When a furnace is installed in public
garages, airplane hangars, or other buildings having hazardous
atmospheres, the unit must be installed in accordance with the
recommended good practice requirements of the National Fire
Protection Association, Inc.
Step 2—Air for Combustion and Ventilation
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3, Air for Combustion and
Ventilation, of the NFGC or applicable provisions of the local
building codes.
Canadian installations must be in accordance with Section 7 of the
NSCNGPIC and all authorities having jurisdiction.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol sprays, deter-
gents, bleaches, cleaning solvents, salts, air fresheners, and
other household products.
All fuel-burning equipment must be supplied with air for combus-
tion of the fuel. Sufficient air MUST be provided to ensure there
will not be a negative pressure in the equipment room or space. In
addition, a positive seal MUST be made between the furnace
cabinet and the return-air duct to prevent pulling air from the
burner area and draft safeguard opening into the circulating air.
The operation of exhaust fans, kitchen ventilation fans,
clothes dryers, or fireplaces could create a negative air
pressure condition at the furnace. Make-up air must be
provided for these devices, in addition to that required by the
furnace.
The requirements for combustion and ventilation air depend upon
whether the furnace is located in a CONFINED or UNCONFINED
space.

UNCONFINED SPACE

An unconfined space has volume of at least 50 cu ft for each 1000
Btuh of total input for all the appliances (such as furnaces, clothes
dryers, water heaters, etc.) in the space.
For Example:
58UHV AND 58UXV FURNACES
HIGH-STAGE INPUT BTUH
60,000
80,000
100,000
117,000
If the unconfined space is of unusually tight construction, air for
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion
and ventilation openings must be sized the same as for a confined
space as defined below. Return air must not be taken from the
room unless an equal or greater amount of air is supplied to the
room.

CONFINED SPACE

A confined space has volume of less than 50 cu ft per 1000 Btuh
of the total input rating for all appliances installed in that space. A
confined space MUST have 2 permanent openings, 1 within 12 in.
of the ceiling, and the other within 12 in. of the floor which freely
communicate with an unconfined space or the outdoors. (See Fig.
2.)
NOTE: In determining the free area of an opening, the blocking
effect of the louvers, grilles, and screens must be considered. If the
free area of a louver or grille design is unknown, it may be
assumed that wood louvers have a 20 percent free area, and metal
louvers or grilles have a 60 percent free area. Screens, when used,
must not be smaller than 1/4-in. mesh. Louvers and grilles must be
constructed so they cannot be closed.
The size of the openings depends upon whether the air comes from
outside of the structure or an unconfined space inside the structure.
1. All air from inside the structure:
a. Each opening MUST have at least 1 sq in. of free area per
1000 Btuh of the total input for all equipment within the
confined space, but not less than 100 sq in. per opening.
(See Fig. 2.) The minimum dimension of air openings shall
not be less than 3 in.
4
MINIMUM SQ FT WITH
7-1/2 FT CEILING
400
534
667
780