7-1. Refrigerant Cycle Diagram

P
Pressure measurement
Gauge attaching port
Vacuum pump connecting port
Deoxidized copper pipe
Outer dia.:
9.52mm (10SAVP-E, -ND)
9.52mm (13SAVP-E, -ND)
12.7mm (16SAVP-E, -ND)
Thickness: 0.8mm
4-way valve
(STF-0108Z)
TS
NOTE :
• The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max. 200g)
7. REFRIGERANT CYCLE DIAGRAM
INDOOR UNIT
Indoor heat
exchanger
Cross flow fan
Deoxidized copper pipe
Outer dia. : 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Muffler
Muffler
TD
Compressor
DA111A1F-24F
Outdoor heat
exchanger
Propeller fan
OUTDOOR UNIT
www.ilmalämpöpumput.com
– 23 –
TCJ
T1
Temp. measurement
TC
TA
Strainer
Pulse motor
valve at liquid side
(CAM-B22YGTF-3)
TO
Split capillary
Ø1.2 x 80
Ø1.2 x 80
T1
TE
Temp. measurement
T1
T2
NOTE :
Max.
: 25m
Min.
: 2m
Chargeless : 15m
Charge : 20g/m
(16 to 25m)
Refrigerant amount : 1.05kg
Gas leak check position
Refrigerant flow (Cooling)
Refrigerant flow (Heating)