8-1-4. Prevent-freezing control
The indoor heat exchanger sensor detects refrigerant
vapor temperature in COOL/DRY operation. If the
temperature is below the specified value, compressor
motor speed is reduced so that operation is performed
in temperature below the specified value to prevent-
freezing of indoor heat exchanger.
8-1-5. P.M.V. (Pulse Modulating Valve)
Using P.M.V., refrigerant flow of refrigeration cycle is
varied for the optimum temperature.
After the power has been turned on, when a serial
operation signal is received from indoor at the first
time, or when PMV alarm is detected and the equip-
ment is reactivated, move the valve once until it hits on
the stopper for positioning of the valve. In this case,
ticktack sound may be heard.
8-1-6. Louver control
(1) Vertical air flow louvers
Positions of vertical air flow louvers are
automatically controlled according to the operation
status (AUTO (A), COOL ( ), DRY ( ), HEAT( )
and FAN ONLY (
). Besides, positions of vertical
air flow louvers can be arbitrarily set by pushing the
[FIX] button.
Operation
mode
Cooling and
Fan only
Dry
Heating
Table 8-1-2
Fan
mode
Remote
Speed
Control
(rpm)
H
HIGH
1210
M+
1130
MED+
1110
M
MED
1010
LOW+
910
L+
880
L
LOW
810
L-
780
L+
880
L
810
L-
780
UL
720
SUL
660
H
HIGH
1290
M+
1290
MED+
1200
M
MED
1110
LOW+
1020
L+
1010
L
LOW
930
L-
880
UL
780
SUL
550
- 29 -
(2) Swing
If the [SWING] button is pressed during running
operation, vertical air flow louvers start swinging.
When the [SWING] button is pushed, swinging stops.
8-1.7. Indoor fan control
(1) The indoor fan is operated by the stepless speed
change motor.
(2) For air flow level, speed of the indoor fan motor is
controlled in five steps (LOW, LOW
and HIGH). If AUTO mode is selected, the fan
motor speed is automatically controlled by the
difference between the preset temperature and
the room temperature.
LOW
MED
13NKV
Air flow
Speed
3
(m
/h)
(rpm)
590
1560
530
1430
520
1440
460
1330
410
1230
390
1230
350
1130
330
1030
390
1230
350
1130
330
1030
290
920
260
860
620
1600
620
1560
570
1510
520
1430
470
1330
460
1330
420
1230
390
1230
330
1030
180
750
FILE NO. SVM-05027
+
, MED, MED
LOW+MED
+
=
2
MED+HIGH
+
=
2
16NKV
Air flow
3
(m
/h)
760
700
710
640
600
600
530
470
600
530
470
410
380
780
760
740
700
640
640
600
600
470
310
+