Toshiba MMY-MAP0804HT8JP Service Manual page 190

Air-conditioner (multi type)
Hide thumbs Also See for MMY-MAP0804HT8JP:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
Sub-code
controller
code
0 * : IGBT circuit
1 * : Position detection circuit
error
3 * : Motor lockup error
4 * : Motor current detection
C * : TH sensor temperature
error
D * : TH sensor error
E * : Inverter DC voltage error
(outdoor fan)
Note:
Although letters 0 to F
appear at locations
indicated by " * ",
pleaseignore them.
P22
P22
01: Compressor 1 side
02: Compressor 2 side
03: Compressor 3 side
P26
P26
01: Compressor 1 side
02: Compressor 2 side
03: Compressor 3 side
P29
P29
P31
Location
of
Description
detection
IPDU
Outdoor fan
IPDU error
IPDU
G-TR short-
circuit protection
error
IPDU
Compressor
position
detection circuit
error
Indoor
Other indoor
unit
error
(group follower
unit error)
Error detection
System status
All stop
(Sub code: 0 )
Fan IPDU over current
protection circuit
Flow of current equal to or
greater than the specified
value is detected during
startup of the fan.
All stop
(Sub code: 1 )
Fan IPDU position detection
circuit
Position detection is not
going on normally.
All stop
(Sub code: 3 )
Gusty wind, an obstruction,
or another external factor
Speed estimation is not
going on normally.
All stop
(Sub code: 4 )
Fan IPDU over current
protection circuit
Flow of current equal to or
greater than the specified
value is detected during
operation of the fan.
All stop
(Sub code: C )
Higher temperature than the
specified value is detected
during operation of the fan.
All stop
(Sub code: D )
The resistance value of the
sensor is infinite or zero
(open or short circuit).
All stop
(Sub code: E )
Fan IPDU DC voltage
protection circuit
The DC voltage higher or
lower than the specified
value is detected.
All stop
Overcurrent is momentarily
detected during startup of
compressor.
All stop
Position detection is not
going on normally.
Stop of
There is error in other indoor
corresponding
unit in group, resulting in
unit
detection of E07/L07/L03/
L08.
– 189 –
Check items (locations)
condition(s)
• Check fan motor.
• Check for defect in fan
IPDU P.C. board.
• Check fan motor.
• Check connection of fan
motor connector.
• Check for defect in fan
IPDU P.C. board.
• Check fan motor.
• Check for defect in fan
IPDU P.C. board.
• Check fan motor.
• Check connection of fan
motor connector.
• Check for defect in fan
IPDU P.C. board.
• Check fan motor.
• Check for defect in fan
IPDU P.C. board.
• Check for defect in fan
IPDU P.C. board.
• Check power voltage of
the main power supply.
• Check for defect in fan
IPDU P.C. board.
• Check connection of fan
IPDU P.C. board.
• Check connector
connection and wiring on
A3-IPDU P.C. board.
• Check for defect in
compressor (layer short-
circuit).
• Check for defect in
outdoor P.C. board (A3-
IPDU).
• Check wiring and
connector connection.
• Check for compressor
layer short-circuit.
• Check for defect in A3-
IPDU P.C. board.
• Check indoor P.C. board.

Hide quick links: