Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit's interface
P.C. board
SW13, 14
(Line (system) address)
Dip switch 2 of SW30
(Terminator of indoor/
outdoor communication
line and central control
line)
Connect after
Relay connector
Header unit
U3 U4
U1 U2
U5 U6
Relay
connector
U
1
U
2
A
B
Remote
controller
Individual
Indoor units
(automatic setting)
Line (system) address
Indoor unit address
Group address
CAUTION
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all
the refrigerant lines. Otherwise, the addresses cannot be set correctly.
Header unit
Follower unit
(No setting
1
required)
(No setting
ON
required)
setting
Open
addresses.
Follower unit
Header unit
U3 U4
U1 U2 U5 U6
Relay
connector
U
1
U
2
A
B
Remote
controller
1
1
1
2
0
0
*The items in bold font must be set manually.
Header unit
Follower unit
(No setting
2
required)
Set to OFF
(No setting
after setting
required)
addresses.
Connect after
setting
Open
addresses.
Follower unit
U3 U4
U3 U4
U1 U2 U5 U6
U1 U2 U5 U6
U
1
U
2
U
1
U
2
A
B
A
B
Remote
controller
Group
2
2
1
2
1
2
– 127 –
Header unit
Factory default
3
1
Set to OFF
after setting
ON
addresses.
Connect after
setting
Open
addresses.
Header unit
U3 U4
U1 U2
U5 U6
Relay
connector
U
1
U
2
A
B
Remote
controller
3
1
0
Central
remote
controller