Specifications; Table 8 Ups Specifications - Liebert GXT2-6000 RT208 User Manual

120/208v; 120/240v
Table of Contents

Advertisement

14.0 S
PECIFICATIONS
Table 8
UPS specifications
Model Number
Model Rating
DIMENSIONS in (mm)
Unit W x D x H in. (mm)
Shipping W x D x H in. (mm)
WEIGHT lbs (kg)
INPUT AC PARAMETERS
Nominal Operating Frequency
Factory Default VAC
L1-L2 Factory Default Input Phase
Allowable Input Phase Angle
Factory Default L1-N, L2-N VAC
User Configurable L1-N, L2-N VAC
L1-N, L2-N, Operating Voltage Range Without Battery Operation (Except 100 VAC L-N Operation)
100% - 90% loading
90% - 70% loading
70% - 30% loading
30% - 0% loading
L1-N, L2-N, Operating Voltage Range Without Battery Operation (100 VAC L-N Operation)
100% - 70% loading
70% - 30% loading
30% - 0% loading
L1-N, L2-N Max. Allowable VAC
Input Frequency w/o Battery
Input Power Connection
OUTPUT AC PARAMETERS
Factory Default VAC
L1-L2 Factory Default
Output Phase Angle
Allowable Output Phase Angle
Factory Default L1-N, L2-N VAC
User Configurable L1-N, L2-N VAC
Output Connections
Main Mode Overload
Bypass Protection Limits
Disable Bypass operation
Re-enable Bypass operation
Disable Bypass operation
Unit
Shipping
Angle
120, 180, 240 degrees, Auto-sensing on application of AC
100/110/115/120/127 VAC (May be modified using configuration program)
Operation
120, 180, 240 degrees Auto-sensing on initial application of input AC
Frequency
Waveform
200% for 8 cycles; 130% for 10 seconds with transfer to bypass
If input voltage returns to within ±10% of nominal output voltage
When the input frequency prevents synchronous operation
GXT2-6000RT208
4200W/5200VA at 127/220 (120 or 240 degrees only)
4200W/5200VA at 120/208 (120 or 240 degrees)
4200W/6000VA at 120/240 (180 degrees)
4200W/6000VA at 115/230 (180 degrees only)
3780W/5400VA at 110/220 (180 degrees only)
3360W/4800VA at 100/200 (180 degrees only)
6.9 x 24.2 x 16.9 (176 x 615 x 430)
13.2 x 27.8 x 20.9 (335 x 705 x 530)
67 (30.3)
76.3 (34.6)
50 or 60 Hz (Factory Default = 60)
120/208 VAC at 120 degrees
120 degrees
(Restrictions for L-N voltages other than 120 VAC)
120 VAC nominal
90 VAC - 140 VAC
80 VAC - 140 VAC
70 VAC - 140 VAC
60 VAC - 140 VAC
80 VAC - 140 VAC
70 VAC - 140 VAC
60 VAC - 140 VAC
150 VAC
40 - 70 Hz
See Distribution Box Options
120/208 VAC @ 120 degrees
120 degrees
120 VAC nominal
100/110/115/120/127 VAC, ±3%
See Distribution Box Options
50 Hz or 60 Hz, Nominal
Sinewave
If input voltage exceeds ±15% of the nominal voltage
41

Specifications

Hide quick links:

Advertisement

Table of Contents
loading