Table 7 Battery Run Times - Liebert GXT2-6000 RT208 User Manual

120/208v; 120/240v
Table of Contents

Advertisement

Using the configuration program, the user may specify the number of GXT2-144VBATT external bat-
tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.
Table 7 shows estimated run times at different loads.
Table 7
Battery run times
Battery/External Cabinets
Internal Battery
Internal Battery + 1 External
Battery Cabinet
Internal Battery + 2 External
Battery Cabinets
Internal Battery + 3 External
Battery Cabinets
Internal Battery + 4 External
Battery Cabinets
6000VA Run Time
Load%
in Minutes
10%
75
20%
38
30%
25
40%
18
50%
14
60%
11
70%
9
80%
7
90%
6
100%
5
10%
156
20%
90
30%
62
40%
44
50%
34
60%
28
70%
23
80%
19
90%
16
100%
14
10%
235
20%
137
30%
99
40%
74
50%
58
60%
47
70%
39
80%
33
90%
28
100%
25
10%
313
20%
183
30%
133
40%
103
50%
82
60%
67
70%
55
80%
47
90%
41
100%
36
10%
391
20%
229
30%
166
40%
129
50%
105
60%
87
70%
73
80%
63
90%
54
100%
47
39