5. Next, press the TEST button on the GFCI module and
verify that the green POWER LED turns OFF and the
red fault LED turns ON (Figure 43).
Figure 43. GFCI Module (Red/Fault LED ON)
6. Also verify that the main circuit breaker switch trips to
the OFF position (Figure 44).
Figure 44. Circuit Breaker OFF (GFCI Test)
7. To restore power, press the RESET button on the GFCI
module and verify that the red fault LED turns OFF
and the green power LED should turn ON (Figure 45).
Figure 45. GFCI Module (Green LED ON Reset)
DA7000SSA2/SSA2GH GENERATOR• OPERATION AND PARTS MANUAL — REV. #0 (03/26/15) — PAGE 37
8. Verify that the AC voltmeter is registering a voltage
reading as shown in Figure 46.
Figure 46. AC Voltmeter (120/240V)
NOTICE
It is recommended that the GFCI module be tested
when the generator is initially taken out of the box.
Then, the generator should be tested daily at startup.
CAUTION
The GFCI module is designed to interrupt power when
a ground fault exists to prevent injuries and shock
hazards. DO NOT operate the generator if this test
fails. Consult a qualified electrician for the repair or
replacement of the GFCI module.