R320-ST & R420-ST Power Vent Indoor Gas Fireplace

Venting Components

The following venting components and associated Montigo part
numbers are available for horizontal installations:
A - Termination
C - Flex Sections
D - Rigid Sections
E - Elbows
F - Support Ring & Plate PSPXT-8
G - Firestop
H - Heat Shield
Connectionandinstallationoftheventcomponentsshould
adheretothefollowingguidelines:
■ Connect all vent sections using a minimum of three sheet
metal screws on the outer pipe flue.
■ Ensure the pipe ends male to female slide in a minimum
of 1 1/2" of overlap.
■ Ensure all runs are supported with a minimum of 3 supports
per 10' of venting.
■ When hanging/ supporting venting, ensure that 1" clearance
is maintained on all sides to any combustible material.
■ Ensure when cutting sections of rigid pipe to maintain
integrity of internal supports.
■ Place the springs, supplied with the pipe kit, between the
outer and inner pipes to keep the pipes separate and avoid
any possible hot spots.
■ Montigo recommends the use of a flex section for the final
pipe connected directly to the fireplace offering greater
flexibility of installation and absorption of movement.
■ All exterior joints in venting should be sealed with high heat
silicone RV230.
Page 16
Installation
PVHEX58-300 Wall Mount 5"/8"
PVHFL58-300 Flush Wall Mount
5"/8"
PVHIN58-300 Inline Power Vent
with TMHIN58-40 termination
PFL1
(12" f/f Section)
PFL2
(24" f/f Section)
PFL3
(36" f/f Section)
PFL4
(48" f/f Section)
PFL6
(72" f/f Section)
PXT - 10 (10" f/f Section)
PXT - 20 (20" f/f Section)
PEXT - 1 (12" f/m Section)
PEXT - 2 (24" f/m Section)
PEXT - 3 (36" f/m Section)
PEXT - 4 (48" f/m Section)
PEXT - 6 (72" f/m Section)
PEL-90MM (m/m 90º Elbow)
PEL-90FF ( f/f 90º Elbow)
PEL-90FM ( f/m 90º Elbow)
PEL-45FM ( f/m 45º Elbow)
FS-8
RHS101
Installation of the horizontal power vent module.
Note: See power vent manual for installation instructions.
Refer to Appendix A - Power Vent locations, to ensure the planned
Vertical Power vent location is acceptable.
HeatShields
Installing a Wall Mounted RHS101 Heat shield
The RHS101 Heat shield mustbeusedifventpipepassesthrough
awallorceilingwithin6'oftheunit.
To install the RHS101, Slide the Inner Section over the vent pipe
that will connect to the fireplace. Then fasten the vent pipe to the
back of the fireplace with a minimum of three sheet metal screws.
From the outside slide the RHS101 outer section on. To complete
the installation fasten the Heat Shield Outer Section & inner section
to the structure. See Figure 8 Sec.4.
3/8" Min. Both sides Typical
3/8" Min.
Figure 8 Sec.4 RHS101 Installation. (Install by sliding over vent pipe
where it passes through the combustible construction).
Inner Shield 9 3/8"
Outer Shield 10 1/4"
Combustible Framing
12" x 12"
XG0774 - 150121