Contents
Before installation.............................................................................. 1
Selecting installation site ................................................................... 2
Preparations before installation......................................................... 2
Indoor unit installation ....................................................................... 3
Installing the duct .............................................................................. 3
Refrigerant piping work ..................................................................... 4
Drain piping work .............................................................................. 5
Electric wiring work ........................................................................... 6
Wiring example ................................................................................. 8
Installation of the decoration panel.................................................... 9
Test operation.................................................................................... 9
Wiring diagram ................................................................................ 10
The English text is the original instruction. Other languages are
translations of the original instructions.
READ THESE INSTRUCTIONS CAREFULLY BEFORE
INSTALLATION. KEEP THIS MANUAL IN A HANDY
PLACE FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO THE EQUIPMENT. BE SURE ONLY
TO USE ACCESSORIES MADE BY DAIKIN WHICH ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.

Before installation

Leave the unit inside its packaging until you reach the
installation site. Where unpacking is unavoidable, use a sling of
soft material or protective plates together with a rope when
lifting, this to avoid damage or scratches to the unit.
When unpacking the unit or when moving the unit after
unpacking, be sure to lift the unit by holding on to the hanger
bracket without exerting any pressure on other parts, especially
on refrigerant piping, drain piping and other resin parts.
Refer to the installation manual of the outdoor unit for items not
described in this manual.
Caution concerning refrigerant series R410A:
The connectable outdoor units must be designed exclusively for
R410A.
1
Split System air conditioners
Precautions
Page
Do not install or operate the unit in rooms mentioned below.
Places with mineral oil, or filled with oil vapour or spray like in
kitchens. (Plastic parts may deteriorate.)
Where corrosive gas like sulphurous gas exists. (Copper
tubing and brazed spots may corrode.)
Where volatile flammable gas like thinner or gasoline is used.
Where machines generating electromagnetic waves exist.
(Control system may malfunction.)
The unit should be installed at least 2.5 m from the floor.
Where the air contains high levels of salt such as air near the
ocean and where voltage fluctuates a lot (e.g. in factories).
Also in vehicles or vessels.
Do not install accessories on the casing directly. Drilling holes in
the casing may damage electrical wires and consequently cause
fire.
Sound pressure level is less than 70dB(A).
Accessories
Check if the following accessories are included with your unit.
Metal clamp
1 piece
Large sealing pad
1 piece
Screws for fixing panels are attached to the air inlet panel.
Optional accessories
There are two types of remote controllers: wired and wireless.
Select a remote controller according to customers request and
install in an appropriate place.
Refer to catalogues and technical literature for selecting a
suitable remote controller.
When installing bottom suction: air inlet panel and canvas
connection for the air inlet panel.
Installation manual
Drain hose
Washer for
1 piece
hanging bracket
8 pieces
Insulation for
Long sealing
fitting
2 pieces
for liquid pipe
1 piece
for gas pipe
1 piece
Screws for duct flanges
1 set
40 pieces.
1
2
Medium
sealing pad
2 pieces
Installation and
operation manual
4 tie wraps

Advertisement

Table of Contents
loading