Operating advanced function
Operating advanced function
FIELD SETTING MODE
Water Law & Room Thermostat : Code 20✴✴
Main Menu &
Code
Water Law
Outdoor Temp for Water Law
(Heating)
Code 20✴✴
Water Out Temp for WL1 Heating
(WL1-Floor)
Water Out Temp for WL2 Heating
(WL2-Fan Coil Unit)
Heating Water Law for Auto Mode
Outdoor Temp for Water Law
(Cooling)
Water Out Temp for WL1 Cooling
(WL1-Floor)
Water Out Temp for WL2 Cooling
(WL2-Fan Coil Unit)
Cooling Water Law for Auto Mode
External Thermostat Application
Water Law for Heating
• Outdoor air temperature range : Lower limit
- With this default settings, the water outlet temperature by heating water law can be
changed within the outdoor temperature range of -10 ~ 15˚C.
• Water out temperature range for floor/FCU applications respectively :
Upper limit
Default 25/35˚C, Range : 17 ~ 37˚C)
- With this default settings, the water outlet temperature by heating water law can be
changed within the range of 25/35 ~ 40/50˚C.
• Type of water law for according to heating devices(floor/FCU) : #3041(Default "1"(WL1 for
floor)), "2"(WL2 for FCU or radiator)
• The #2 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the water outlet temperature.
• The operation mode of the wired remote controller should be set to "AUTO"(
the weather dependent water law scheme.
36_ Operating advanced function
Ts
#2021/2031
#2022/2032
#2061/2071
#2062/2072
Heating WL
Floor FCU
#2011
������������������������������
Field Setting Value
���������������������������������������������������
Sub Menu Function
Upper limit
(#2021/2031, Default 40/50˚C, Range : 40 ~ 55˚C), Lower limit
Cooling WL
#2012
#2051
#2052
Sub
Description
Code
Point
✴✴11
Point
✴✴12
Point
✴✴21
Point
✴✴22
Point
✴✴31
Point
✴✴32
WL Type
✴✴41
Point
✴✴51
Point
✴✴52
Point
✴✴61
Point
✴✴62
Point
✴✴71
Point
✴✴72
WL Type
✴✴81
#1(Floor)
✴✴91
#2(FCU)
✴✴92
(#2011, Default -10˚C, Range : -20 ~ 5˚C),
(#2012, Default 15˚C, Range : 10 ~ 20˚C)
Shift Value
����������
Ta
Default
Min
Max
Step
-10
-20
5
1
15
10
20
1
40
40
55
1
25
17
37
1
50
40
55
1
35
17
37
1
1(WL1)
1
2(WL2)
-
30
25
35
1
40
35
45
1
25
18
25
1
18
5
18
1
18
18
25
1
5
5
18
1
1(WL1)
1
2(WL2)
-
0(No)
0
1(Yes)
-
0(No)
0
1(Yes)
-
(#2022/2032,
Unit
˚C
˚C
˚C
˚C
˚C
˚C
-
˚C
˚C
˚C
˚C
˚C
˚C
-
-
-
) to use