Remote Controller Setting Range : Code 10✴✴
Main Menu &
Sub Menu Function
Code
Remote
Water Out Temp for Cooling
Controller
Setting Range
Room Temp for Cooling
Code 10✴✴
Water Out Temp for Heating
Room Temp for heating
DHW Tank Temp
Space Cooling
• Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC),
- With this default FSV settings, user can change the target water outlet temperature within
the range of 5 ~ 25ºC for cooling
• Target room temperature : Upper limit(#1021, Default 30ºC, Range : 24 ~ 30ºC),
- With this default FSV settings, user can change the target room temperature within the
range of 18 ~ 30ºC for cooling.
• The #1 DIP switch in the wired remote controller should be set to "OFF"(Default) for
cooling operation of heat pump.
• The #2 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the water outlet temperature.
• The #2 DIP switch in the wired remote controller should be set to "ON" to control the
room temperature.
• The #3 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the air sensor in remote controller.
Space Heating
• Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC),
- With this default FSV settings, user can change the target water outlet temperature within
the range of 25 ~ 55ºC for heating.
• Target room temperature : Upper limit(#1041, Default 30ºC, Range : 24 ~ 30ºC),
- With this default FSV settings, user can change the target room temperature within the
range of 16 ~ 30ºC for heating.
• The #2 DIP switch in the wired remote controller should be set to "OFF"(Default) to
control the water outlet temperature.
• The #2 DIP switch in the wired remote controller should be set to "ON" to control the
room temperature.
DHW Heating
• Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 80ºC),
- With this default FSV settings, user can change the target tank temperature within the
range of 40 ~ 50ºC for DHW heating.
• The FSV #3011 in the wired remote controller should be set to "1(Yes)" to use DHW
function.
• The #3 DIP switch in the wired remote controller should be set to "ON" to control the
external air sensor.
Field Setting Value
Description
Max
Min
Max
Min
Max
Min
Max
Min
Max
Min
Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)
Lower limit(#1022, Default 18ºC, Range : 18 ~ 22ºC)
Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)
Lower limit(#1042, Default 16ºC, Range : 16 ~ 22ºC)
Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)
Sub
Default
Min
Max
Code
25
18
✴✴11
16
5
✴✴12
30
24
✴✴21
18
18
✴✴22
55
37
✴✴31
25
15
✴✴32
30
24
✴✴41
16
16
✴✴42
50
50
✴✴51
40
30
✴✴52
Operating advanced function _35
Step
Unit
25
1
˚C
18
1
˚C
30
1
˚C
22
1
˚C
55
1
˚C
37
1
˚C
30
1
˚C
22
1
˚C
65
1
˚C
40
1
˚C