Precautions regarding test-runs
If the remote control shows E0, E3 or E4 as an error code, there
is a possibility that either the shut-off valve is closed, or the
outlet vent is closed.
For reverse or missing phase, U1 will be displayed on the
remote control for the indoor unit, and operation will be
impossible. If this happens, turn off the power, re-check the
wiring and switch the position of two of the three electrical wires.
(If operation is not possible, do not under any circumstances
force the electromagnetic contactor on.)
If the error code E6 is displayed on the remote contol, check for
voltage imbalance.
If the error code UF is displayed on the remote contol, check the
inter-unit branch wiring connection.
Diagnosis
On the remote control LCD
If the machine stops due to some malfunction, you can diagnose
the problem using the error code displayed on the remote
control.
Error code
Description
Safety device activated (indoor/outdoor fan malfunction,
E0
compressor malfunction, electric motor malfunction)
F6
Heat exchange temperature malfunction
J2
Electric current sensor malfunction
-
The malfunction code should be looked up in the installation
manual for the indoor unit.
-
Depending on the indoor unit or outdoor unit type, error
codes may not be displayed.
D
ISPOSAL REQUIREMENTS
Dismantling of the unit, treatment of the refrigerant, oil and any other
parts should be done in accordance with the relevant local and
national regulations.
R(Y)P71~125L7V1+W1
Split System air conditioners
4PW14486-1B
N
OTES
Installation manual
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents