Typical Parts List ....................................4 Introduction This manual provides general information about the Ultravi- olet Light option for Daikin RoofPak® applied rooftop models RPS/RDT/RFS/RPE/RDE/RDS and RAH. In addi- WARNING tion to an overall description of the unit, it includes removal UVC exposure is harmful to the skin and eyes.
Operation Refer to the Wiring Schematic below. 115 VAC power for the The normally open disconnect switches are wired in series in a UV lights is provided by control circuit transformer T1. The circuit that supplies 24VAC to the coil of relay R45. When all lights operate whenever the unit is powered, system switch S1 doors are closed, relay R45 is energized, and its normally open is closed, and all doors with door power disconnect switches...
3. Carefully slide the lamp units off the rail. Use the slots in the rail if needed to help in removal. Place the lamp unit on a flat surface. Replacement Parts List Figure 3. Removing Lamp Units - Step 1 Daikin PN Description 033696300 Power Disconnect Switch 205484001 18 in.