When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knock-out hole.
(See figure 6)
1
Wire
2
Bush
3
Nut
4
Frame
5
Hose
A
Inside
B
Outside
When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knock-out hole from
cutting the wires.
Follow the electric wiring diagram for electrical wiring works.
Form the wires and fix the cover firmly so that the cover may be
fit in properly.
Precautions on wiring of power supply and inter-unit
wiring
Use a round crimp-style terminal for
connection to the power supply
terminal board. In case it cannot be
used due to unavoidable reasons,
be sure to observe the following
instruction.
-
Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
-
When connecting wires of the same gauge, connect them
according to the below figure.
Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
See the tabel below for tightening torques for the terminal
screws.
Tightening torque (N•m)
M4
1.32~1.62
M5
2.21~2.70
Refer to the installation manual attached to the indoor unit for
wiring of indoor units, etc.
Attach an earth leak detector and fuse to the power supply line.
(See figure 8)
I
Pair
II
Twin
III
Triple
M
Master
S
Slave
Earth leak detector
1
Fuse
2
Remote controller
3
In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.
Installation manual
10
Specifications of standard wiring components
Power supply
Field
Model
fuse
Wire type
R(Y)P71L7V1
32A
H05VV-U3G
R(Y)P100L7V1
40A
H05VV-U3G
R(Y)P71L7W1
16A
H05VV-U5G
R(Y)P100L7W1
16A
H05VV-U5G
R(Y)P125L7W1
20A
H05VV-U5G
(1) Only in protected pipes, use HO7RN-F when protected pipes are not used.
T
EST OPERATION
Be sure to fully open the liquid-side and gas-side stop valves.
For details on test operation, refer to the indoor unit installation
manual.
Pre-run checks
Items to check
Electrical wiring
Is the wiring as mentioned on the wiring
Inter-unit wiring
diagram?
Ground wire
Make sure no wiring has been forgotten and that
there are no missing phases or reverse phases.
Is the unit properly grounded?
Are any of the wiring attachment screws loose?
Refrigerant piping
Is the size of the piping appropriate?
Is the insulation material for the piping attached
securely?
Are both the liquid and gas pipes insulated?
Are the shut-off valves for both the liquid side and
the gas side open?
Extra refrigerant
Did you write down the extra refrigerant and the
refrigerant piping length?
Test run
1
Make sure the liquid and gas shut-off valves are open.
B
A
Be sure to close the frontside panel before operation, as not
doing so can cause electric shock.
-
The refrigerant pressure may not rise, even if the shut-off
valve is opened after an air purge is performed using a
vacuum pump.
This is because the indoor unit refrigerant piping is closed off
with electric valves inside. This will not create any problems
during operation.
2
Be sure to set it to cooling and press the operation switch.
3
Press the inspection/test-run switch on the remote control to put
the machine into test-run mode.
4
Make sure the compressor is not starting and stopping during
the test-run by listening. If it is starting and stopping,
immediately stop the machine using the remote control, and
check the refrigerant level, etc. There may be some sort of
malfunction.
Wire type
of wiring
between
(1)
Size
the units
H05VV-U4G2.5
Wiring size
must comply
H05VV-U4G2.5
with the
applicable
H05VV-U4G2.5
local
H05VV-U4G2.5
and national
code
H05VV-U4G2.5
Opening direction
A
Liquid side
B
Gas side
Remove the cap and turn
counterclockwise with a
hex wrench until it stops
R(Y)P71~125L7V1+W1
Split System air conditioners
4PW14486-1B